2-12
List of Settings
Section 2
Lis
t of
Se
ttings
Initial Setting Level
Note
The values beginning with H' in the
Monitor/Setting range
column are used when setting or monitor-
ing data via communications.
Input Adjustment Level
Note
The values beginning with H' in the
Monitor/Setting range
column are used when setting or monitor-
ing data via communications.
Variable
type
Address
Parameter
name
Charac-
ter
Monitor/Setting range
Character
Default
setting
Decimal point
Unit
C4
0010
Function
func
H’00000000 to H’00000005: (F1 to 6)
f1
to
6
f1
---
---
0001
Input type A
in-ta
H’00000000: No-contact (NO)
H’00000001: No-contact (NC)
H’00000002: Contact (NO)
H’00000003: Contact (NC)
00
,
01
,
10
,
11
00
---
---
0007
Input type B
in-tb
H’00000000: No-contact (NO)
H’00000001: No-contact (NC)
H’00000002: Contact (NO)
H’00000003: Contact (NC)
00
,
01
,
10
,
11
00
---
---
0011
Prescale AX
ps.
ax
H’00000000 to H’0001869F: (0.0000 to 9.9999)
0.
0000
to
9.
9999
1.
0000
4
---
0012
Prescale AY
ps.
ay
H’FFFFFFF7 to H’00000009: (
−
9 to 9)
10 -9
to
10 9
10 0
---
---
0013
Prescale BX
ps.
bx
H’00000000 o H’0001869F: (0.0000 to 9.9999)
0.
0000
to
9.
9999
1.
0000
4
---
0014
Prescale BY
ps.
by
H’FFFFFFF7 to H’00000009: (
−
9 to 9)
10 -9
to
10 9
10 0
---
---
0015
Time unit
time
H’00000000: OFF (0)
H’00000001: min (1)
H’00000002: hour: min: s (2)
H’00000003: min, s: 100 ms (3)
off
,
min
,
h.
mm.
ss
,
mm.
ss.
d
off
---
---
000D
Decimal point
position
dp
H’00000000 to H’00000004: (0 to 4)
\\\\\
,
\\\\.
\
,
\\\.
\\
,
\\.
\\\
,
\.
\\\\
\\\\\
---
---
000E
Comparative
output pattern
out-p
H’00000000: Standard outputs (0)
H’00000001: Zone outputs (1)
H’00000002: Level outputs (2)
nomal
,
zone
,
level
nomal
---
---
Variable
type
Address
Parameter
name
Charac-
ter
Monitor/Setting range
Character
Default
setting
Decimal point
Unit
C5
0006
Averaging type
a?g-t
H’00000000: Simple average (0)
H’00000001: Moving average (1)
smpl
,
mo?e
smpl
---
---
0007
Averaging times
a?g-n
H’00000000: 1 (0)/H’00000001: 2 (1)/
H’00000002: 4 (2)/H’00000003: 8 (3)/
H’00000004: 16 (4)/H’00000005: 32 (5)/
H’00000006: 64 (6)/H’00000007: 128 (7)/
H’00000008: 256 (8)/H’00000009: 512 (9)/
H’0000000A: 1,024 (10) times
1
,
2
,
4
,
8
,
16
,
32
,
64
,
128
,
256
,
512
,
1024
1
---
---
000C
Auto-zero time A
at.
za
H’00000000 to H’0000752F: (0.0 to 2999.9)
0.
0
to
2999.
9
2999.
9
1
s
000D
Auto-zero time B
at.
zb
H’00000000 to H’0000752F: (0.0 to 2999.9)
0.
0
to
2999.
9
2999.
9
1
s
0010
Power supply
memory
memo
H’00000000: OFF (0), H’00000001: ON (1)
off
,
on
off
---
---
Summary of Contents for K3HB
Page 2: ...K3HB Digital Indicators Communications User s Manual Revised March 2005...
Page 3: ...iv...
Page 15: ...xvi...
Page 19: ...xx...
Page 21: ...Part 1 CompoWay F...
Page 69: ...Part 2 DeviceNet...
Page 95: ...6 10 Ladder Programming Examples Section 4 3 Remote I O Com munications...
Page 111: ...8 8 Message Communications Performance Section 6 2 Communications Performance...
Page 127: ...Part 3 BCD Output...
Page 147: ......