Operation manual
G9SR
Page 58 of 79
11.1.4
G9SR-
BC□
-
□ for
d
oor interlocking up to PLd with F3S
-TGR-N__C
Settings G9SR-BC:
•
Manual Restart enabled
•
EDM enabled
•
Dynamic Input Test disabled
•
Aux inverted
Dip switch settings: 1
2
3
4
5
6
7
8
OFF OFF ON
OFF OFF OFF OFF OFF
Description:
Non-contact switch connected to T12 and T22
Restart pushbutton connected to T31
KM1 and KM2: Motor Contactors
Feedback loop (EDM) connected to T32
Remarks:
This setup can also be used with safety limit switches and key operated door switches.
For door and gate monitoring applications please consider the requirements from ISO
14119.
Applicable up to PLd acc. EN ISO 13849-1 (electrical system).
Motor circuit (contacts of KM1 and KM2) not shown.