9.1
Wiring examples stand-alone G9SR-BC
9.1.1
G9SR-BC wiring with dynamic testing with EDM
Function setting:
DIP Switch 1 OFF
= Manual Restart
DIP Switch 2 ON
= Dynamic input testing Enabled
DIP Switch 3 ON
= EDM Enabled
Description:
E-Stop pushbutton connected to T12 and T22
Restart pushbutton connected to T31
KM1 and KM2: Motor Contactors
Feedback loop (EDM) connected to T32
Remarks:
Wiring is using the dynamic test pulses.
Applicable up to PLe acc. EN ISO 13849-1
Motor circuit (contacts of KM1 and KM2) not shown.
Power
supply
circuit
Safety
Input 1
Safety
Input 2 Restart
EDM
Safety Output
Control
Auxiliary Output
Control
T32
T31
T22
T21
T12
A1
A2
14
24
44
KM1
KM2
T11
KM1
KM2
+24V
0V
Fuse
5A F
Figure 5 - G9SR-BC wiring with dynamic testing with EDM