Operation manual
G9SR
Page 20 of 79
4
3
2
1
ON
8
7
6
5
4
3
2
1
ON
8
7
6
5
6.3
Dip switches and functions of G9SR-
BC□
-
□
The DIP-Switches are used to configure the G9SR-BC unit for the
application.
There are two banks of DIP-switches in the G9SR-BC.
Both DIP-switch banks have eight switches.
To select a function, the switches on both DIP-switch banks
have to be set identically.
Example:
DIP SWITCH 3, BANK1 = "OFF"
and
DIP SWITCH 3, BANK2 = "OFF" => OK
DIP SWITCH 3, BANK1 = "OFF"
and
DIP SWITCH 3, BANK2 = "ON" => ERROR
Caution
!
Do not change the setting of the DIP switches during operation of
the G9SR-BC. In this case, the G9SR-BC will change the outputs
to "OFF" and will enter a lockout state.
Use the switches to configure following functions:
Function
Switch
G9SR-
BC□
-
□
Restart
1
ON = Auto Restart
OFF = Manual Restart
Dynamic Input Testing 2
ON = Enabled
OFF = Disabled
EDM
3
ON = Enabled
OFF = Disabled
INPUT LOOP
4
ON = input loop enabled.
This disables the OSSDs and Aux out.
OFF = input loop disabled
AUX OUT STATUS
5
ON = Aux out status consistent with OSSD
OFF = Aux out status inverted.
6/7/8
Reserved
B
A
N
K
1
B
A
N
K
2
Summary of Contents for G9SR
Page 1: ...ZX T Series Cat No J12E EN 03 G9SR Safety Relays OPERATION MANUAL G9SR BC G9SR AD G9SR EX...
Page 34: ...Operation manual G9SR Page 8 of 79 3 1 Test the OFF behaviour...
Page 35: ...Operation manual G9SR Page 9 of 79 3 2 Test the ON behaviour...
Page 102: ...Operation manual G9SR Page 76 of 79 My notes...
Page 105: ...Operation manual G9SR Page 79 of 79 My notes...