![background image](http://html1.mh-extra.com/html/omron/g9sr/g9sr_operation-manual_743828048.webp)
Operation manual
G9SR
Page 22 of 79
6.4.4
EDM LED
= External Device Monitoring
Color: Yellow
ON when EDM function is enabled.
FLASH when any error on External Device Monitoring occurs.
See also § 6.5.2
on page 24
OFF EDM function is disabled.
6.4.5
ON LED
= Outputs
Color: Green
ON when the outputs are activated = ON.
FLASH fast (3 per second) when input-loop chain is OK.
OFF when the outputs are de-activated = OFF.
6.4.6
OFF/ERR LED = OFF & Error
Color: Red
ON when OSSDs are OFF
FLASH when an error occurs (EDM and Restart leds provide error code).
Fast blinking & RES or COM fast blinking
= Communication error of another unit
Slow blinking = OSSD error.
Slow blinking & RES or COM slow blinking
= Communication error of this unit.
See also § 6.5.2
OFF when all internal diagnostics are successfully passed and OSSDs are
activated = ON.
Summary of Contents for G9SR
Page 1: ...ZX T Series Cat No J12E EN 03 G9SR Safety Relays OPERATION MANUAL G9SR BC G9SR AD G9SR EX...
Page 34: ...Operation manual G9SR Page 8 of 79 3 1 Test the OFF behaviour...
Page 35: ...Operation manual G9SR Page 9 of 79 3 2 Test the ON behaviour...
Page 102: ...Operation manual G9SR Page 76 of 79 My notes...