9.2.4
G9SR-AD wiring without dynamic testing without EDM
Function setting:
DIP Switch 1 OFF
= Manual Restart
DIP Switch 2 OFF
= Dynamic input testing Disabled
DIP Switch 3 OFF
= EDM Disabled
Description:
E-Stop pushbutton connected to T12 and T22
Restart pushbutton connected to T31
KM1 and KM2: Motor Contactors
Remarks:
Applicable up to PLd acc. EN ISO 13849-1
Motor circuit (contacts of KM1 and KM2) not shown.
Power
supply
circuit
Safety
Input 1
Safety
Input 2 Restart
EDM
Safety Output
Control
Auxiliary Output
Control
IN
Loop
OUT
Loop
K1
K2
K1
K2
A1
T11 T12 T21 T22
T31
T32
13
23
T44
T41
T43
T42
A2
44
14
24
+24V
KM1
KM2
0V
Fuse
1A F
Fuse
5A F
Fuse
5A F
Figure 12 - G9SR-AD wiring without dynamic testing without EDM