4. Setting (Air Flow Station Operation)
4-6
4.2.4 Description of Items
(1)
Data Recording Interval (CYCLE)
Specifies the interval of measured value recording.
The range of selection (Options):
1s (second)/ 2s / 5s / 10s / 20s / 30s / 1m (minute)
Initial value: 1s
(2)
Number of Air Flow Sensor Units Connected (UNIT)
Specifies the number of Air Flow Sensor units to be connected.
The range of selection (Numeric input):
1 to 8
Initial value: 1
(3)
Initialization (INIT)
The unit initializes the setting values and restores the factory defaults (except for year,
month, day, hour and minute settings).
Important
The unit initializes setting values about Air Flow Station itself, not initializes the values about
Air Flow Sensors. Please refer to the following table.
Initializes setting values
Not Initializes setting values
・
Data collection cycle
・
Number of connected Air Flow
Sensors
・
IP address
・
Rate conversion, CO2 conversion and the
conversion unit.
・
Auto backup and restarting record setting
・
Alarm hold setting
・
Year, Month, Day, Hour, Minute, Second
・
Sensor setting values
(Pulse setting, Flow full-scale value,
Averaging count, Measurement target gas)
・
Sensor threshold value (Hi, Lo, Cut)
Operation:
Holding the SET/REC/STOP key starts initialization and it is finished when “DONE” is
displayed. Before showed “DONE”, the initialization is canceled.
After initialization, press the MODE key twice to exit THR mode. The unit is restarted
and the setting values are initialized.