3.3.2 Standalone Operation Connecting Air Flow Sensors to Air Flow Station
(1)
Air Flow Sensor Setting
Set the Unit No. and Termination resister of the Air Flow Sensor unit. Up to 8 Air Flow
Sensor units can be connected to an Air Flow Station, and it is possible to use
D6FZ-FGS1000 and D6FZ-FGT
concurrently.
・
Set Unit No. from 01 in sequence.
・
When more than one sensor is connected with Air Flow Station, communication
terminator of the last sensor must be ON.
< D6FZ-FGS1000 >
This section shows the example of setting five Air Flow Sensor units.
(1) Open the switch cover by removing the screws on the Air Flow Sensor unit.
(2) Make settings on the 1st to 4th units.
DIP SW:
Set the communication terminator (No. 1) to OFF on all the four
units.
See the figure below.
Rotary SW:
Assign ID numbers from 01 to 04.
(3) Make settings on the 5th unit (termination).
DIP SW:
Set the communication terminator (No. 1) to ON.
Rotary SW:
Assign the ID to "05".
Important
DIP SW and rotary SW settings are applied after the unit is reset.