2. Part Name and Function
2-2
2.1.2 Control Unit
(1)
DIP SW
No.
Definition
1
Communication line terminator setting
To use an Air Flow Station (D6FZ-FGX21) or RS-485
communication, turn ON the DIP SW No. 1of the termination Air
Flow Sensor unit in the multi-drop connection.
(Factory default setting: ON)
2
Fixed to OFF (Only used for maintenance. Do not turn it ON)
3
Default communication setting
Use this to reset the settings when changes cannot be tracked
after setting changes.
(Factory default setting: OFF)
Important
DIP SW settings are applied after the unit is reset.
(2)
Rotary SW
Used to specify the IDs of the Air Flow Sensors connected to the Air Flow Station. The
positions from 1 to 8 can be assigned. The ID numbers must be assigned in the ascending
order sequentially without skipping any number.
10's Place 1's Place
(0: Fixed) (Factory default setting: 1)
Important
・
Rotary SW settings are applied after the unit is reset.
・
1's Place is available 1 to 8, don’t set the ID to 0 and 9.