Air Flow Sensor (D6FZ-Series)
<D6FZ-Series>
1. Do not install the product in locations subjected to the following conditions:
・
Ambient temperature outside the rating
・
Ambient humidity outside the rating
・
Altitude of 2,000 m or higher above sea level
・
Presence of corrosive or flammable gases
・
Presence of salt or iron particles
・
Direct vibration or shock
・
Outdoors or direct sunlight
・
Water, oil, or chemical fumes or spray, or mist atmospheres
・
Presence of strong magnetic field, electric field or charged object
2. Power Supply and Wiring
・
If the power supply line is subject to surges, connect a surge absorber that meets the conditions of the
operating environment.
・
Be sure to check the polarity before connecting a power supply line/output line. Do not apply over-rated
voltage.
・
Do not short circuit the power supply when connecting a power supply line.
・
Do not use the product with current higher than the rating when connecting an output line.
・
Lay the product cable away from any high-voltage cable or power line. If laid in the same conduit or duct,
induction noise from them may cause malfunction or breakdown of the product.
・
Do not insert or remove a connector, etc. with power supply applied.
・
When using analog output or control output, cable length needs to be less than 30 m.
・
When using with an Air Flow Station make the power supply voltage 24VDC.
・
When using RS-485 communication and cable length is
more than 30m, be sure to ground blue
colored wire (0V) and shield.
3. Installation
・
When mounting the product, be careful not to get a finger caught in it.
<
D6FZ-FGS1000
>
・
Do not use the product as scaffolding.
・
Take caution not to mount the status indicator downward. Doing so may result in Malfunction.
<
D6FZ-FGT
>
・
Be sure to mount the body horizontally, otherwise the detection accuracy might be worse.
・
Don't mount the body facing the control panel downward. Otherwise, the mist and dust in the pipe
accumulates and it might cause breakdown.