2-2
Section
Note The service life of relay output contacts shown in the table assumes the worst
conditions. The following graph shows the results of OMRON’s service life tests
at a switching rate of 1,800 times/hour.
Life (x 10
4
)
Contact current (A)
120 VAC, resistive load
24 VDC/240 VAC, resistive load
Switching rate: 1,800 times/hour
24 VDC,
τ
= 7 ms
120 VAC, cos
φ
= 0.4
240 VAC, cos
φ
= 0.4
Transistor Outputs (Sinking or Sourcing)
Item
Specification
Max. switching capacity
40 mA/4.5 VDC to 300 mA/20.4 VDC,
300 mA (20.4 VDC to 26.4 VDC)
When using OUT01000 or OUT01001 as a pulse output, connect a dummy resistor as
required to bring the load current between 10 and 150 mA. If the load current is below
10 mA, the ON/OFF response time will be longer and high-speed pulses will not be output.
The transistor will heat if used at 150 mA or higher, possibly damaging elements.
Min. switching capacity
0.5 mA
Max. inrush current
0.9 A for 10 ms (charging and discharging waveform)
Leakage current
0.1 mA max.
Residual voltage
0.8 V max.
ON delay
OUT01000 and OUT01001:
20
µ
s max.
OUT01002 and up:
0.1 ms max.
OFF delay
OUT01000 and OUT01001:
40
µ
s max. 10 to 300 mA
0.1 ms max. 0.5 to 10 mA
OUT01002 and up:
1 ms max.
Fuse
1 fuse for each 2outputs (cannot be replaced by user)
Summary of Contents for CPM2C
Page 1: ...CPM2C Programmable Controllers Operation Manual Produced June 1999...
Page 2: ...http www bzxindaxin com http www gk world com...
Page 3: ...http www bzxindaxin com http www gk world com...
Page 4: ...http www bzxindaxin com http www gk world com...
Page 5: ...http www bzxindaxin com http www gk world com...
Page 6: ......