3-3
Section
# !
•
Orient the CPM2C as shown below when installing it.
Top
Bottom
Power lines and high-voltage equipment can cause electrical noise in the PC.
•
Do not install the CPM2C in a panel or cabinet with high-voltage equipment.
•
Allow at least 200 mm between the CPM2C and nearby power lines.
CPM2C
200 mm min.
200 mm min.
Ensure that the CPM2C can be accessed for normal operation and mainte-
nance.
•
Provide a clear path to the CPM2C for operation and maintenance. High-volt-
age equipment or power lines could be dangerous if they are in the way during
routine operations.
•
The PC will be easiest to access if the panel or cabinet is installed about 1 to
1.6 m above the floor.
•
Separate the CPM2C by at least 100 mm from other devices.
Other
device
100 mm min.
Other
device
100 mm min.
3-3
Installing the CPM2C
This section describes how to install the CPM2C and connect Expansion Units.
Refer to
Appendix B
for diagrams showing the dimensions of the Units.
3-3-1 Connecting Units
Up to 5 Expansion I/O Units can be connected to a CPM2C CPU Unit. Use the
following procedure when connecting an Expansion I/O Unit.
Electrical Noise
Accessibility