E3NW-CRT
User’s Manual
Section 5
Command Descriptions and Data Formats
●
Dummy Sensor Response Setting
This command registers a Dummy Sensor.
If a Dummy Sensor is registered as Unit 1 (i.e., if bit 00 is 1), the actual first Unit (i.e.,
the leftmost Sensor Amplifier Unit) will be Unit 2.
You must restart the Sensor Communications Unit for any changes to the Dummy
Sensor Settings to take affect.
This setting cannot be changed via I/O commands in I/O Mode 2.
●
Dummy Sensor Response Setting
You can specify the response to return when an explicit message is sent to a Dummy
Sensor.
If you select to return a normal completion instead of an error completion, 0000 will be
returned for any read command sent to a Dummy Sensor.
This setting cannot be changed via I/O commands in I/O Mode 2.
●
Sensor Model
This command reads the model of the Sensor Amplifier Unit that corresponds to the
specified unit number.
●
Read Detection Level
This command reads the detection level (incident light level) of the Sensor Amplifier
Unit that corresponds to the specified unit number and output number.
The data is given as the two’s complement of a 4-byte (8-digit) hexadecimal value.
Bit
Description
Data
00 to 15
Dummy Settings
Each bit:
0: Clear Dummy Sensor
1: Register Dummy Sensor
16 to 31
No applicable data
Always 0
Bit
Description
Data
00
Response Mode
0: Return a normal completion instead of an error completion.
1: Return an error completion.
01 to 31
No applicable data
Always 0
Data
Description
0160 hex
E3NX-FA0
0260 hex
E3NC-LA0
0360 hex
E3NC-SA0
Bit
Description
Data
00 to 31
Read Detection Level
Data range:
−
1,999 (FFFFF831 hex) to 9,999 (0000270F hex)