E3NW-CRT
User’s Manual
Section 5
Troubleshooting
SS indicator lit
red
One of the connected Sensor
Amplifier Units is faulty.
Replace the faulty Sensor Amplifier Unit.
You can determine which Sensor Amplifier Unit is faulty by
checking the number of Sensors available for
communications.
One of the connected Sensor
Amplifier Units has been
disconnected.
Connect the Sensor Amplifier Units correctly.
The number of connected
Sensor Amplifier Units exceeds
the maximum allowable
number.
Keep the number of connected Sensor Amplifier Units
within the maximum allowable number.
The total number of connected Sensors, including all
registered Dummy Sensors, must be within the maximum
allowable number.
One of the connected
Distributed Sensor Units has
been disconnected.
There is a problem with the Distributed Sensor Unit
connection. Check the installation of the Distributed Sensor
Unit.
Status
Possible cause
Remedy