background image

6

Installing the panel

1. Align the "PIPING SIDE" and "DRAIN SIDE" sections marked on

the  panel  with  the  corresponding  piping  connector  and  water
discharge connector of the unit.

2. When installing the panel, first hang its hooks on the swing motor

side and opposite side of the panel to the corresponding drainage
pan  hooks  on  the  unit  (see  a  in  the  figure).  Then,  hang  the  two
remaining panel hooks to the corresponding suspension bracket of 
the unit (see b in the figure).

3. Slot the guide wire of the swing motor to the card slot on the panel,

and connect the power supply terminal of the swing motor to the
corresponding connector of the electric control box.

1. Secure the installation cover rope onto the bolt on the installation

cover with screws.

2. Gently press the installation cover into the panel.

4. Adjust the four panel hook screws to keep the panel level, and lift

it evenly up to the ceiling (see a in the figure).

5. Adjust the panel slightly in the direction indicated by d in the figure, 

so that the center of the panel aligns with the center of the opening 
of the ceiling. Verify that the hooks in all four corners are securely
in place.

6. Continue to evenly tighten the screws under the hooks of the panel 

until the foam thickness between the unit and the air outlet on the
panel  is reduced  to  about 4–6  mm,  and  the  panel  has  a  steady
contact with the ceiling surface.

d

Swing motor

Piping side

Drain side

a

b

c

Panel hook

Drainage 
pan hook

Hook screw

Phillips 
screwdriver

Swing motor

Foam at panel side

Unit

Ceiling

Panel

Panel bubble 1

Air outlet Air deflector

Panel bubble 2 

4

–6

 m

m

The  plastic  cover  plate  protruding  from  the swing motor must 
be embedded within the concave area of the sealing plate.
Make  sure  the  wiring  of  the  swing  motor  is  not  caught  inside 
the sealed foam.
Improper  screw  tightening will  result  in  the  fault  shown  in  the 
right figure.
If  there  is  still  a  gap  between  the  ceiling  and  panel  after  the 
screws are tightened, re-adjust the IDU height (Figure I).
Without affecting the lifting, lowering, and levelness of the IDU 
and  the  water  discharge  piping,  you  can  use  the  openings  at 
the four  corners of  the  panel  to adjust  the IDU height (Figure 
II).

First hang the air inlet grille on the panel, and then connect the 
leads  of  the  swing  motor  and  control  box  to  the  corresponding 
connectors on the unit respectively.

Reinstall  the  air  inlet  grille  by  performing  the  steps  used  to 
remove the air inlet grille in the reverse order.

Reinstall the installation cover.

Air
leakage

Ceiling

Droplets of condensed water,
dripping water.

Pollution

No gap allowed

A. First loosen the upper nut

B. Adjust the lower nut

Figure II

Figure I

Bolt

Display part connection wire

Exert pulling force from 
the position for 
installing/removing 
buckle

During the cover installation, slide four 
fasteners into the corresponding slots 
on the panel.

Installation cover rope 

self-tapping screws

Remove the screws from all four corners of the installation cover 
plate to release the cover plate rope, and take out the cover plate, 
facing outwards.

CAUTION

Summary of Contents for OTEC IECS-D Series

Page 1: ......

Page 2: ...sconnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the nat...

Page 3: ...requirement 18 Vacuum pump Charge hose R410A special requirement 19 Torque wrench 20 Copper pipe gauge adjusting projection margin 21 Vacuum pump adapter Required tools for installation work 1 Philip...

Page 4: ...ry if the location is not strong enough Carry out the specified installation works to prevent strong winds or earthquakes Improper installation may cause the unit to drop leading to accidents Before w...

Page 5: ...ling when necessary b Adjust the position of the unit and make sure that the gap with the ceiling is evenly spaced on all four sides of the unit and the base of the unit is 10 12 mm into the base of t...

Page 6: ...therwise it may cause water to leak Calibrate the levelness of the IDU using a spirit level or polyethylene tube filled with water The IDU is equipped with a built in drain pump and float switch Do no...

Page 7: ...ook Drainage pan hook Hook screw Phillips screwdriver Swing motor Foam at panel side Unit Ceiling Panel Panel bubble 1 Air outlet Air deflector Panel bubble 2 4 6 mm The plastic cover plate protruding...

Page 8: ...outdoor unit and the indoor unit may not exceed the allowable piping length In the case that the installation place is exposed to strong wind such as a seaside make sure the fan operating properly by...

Page 9: ...from becoming loose When the outlet of the water discharge pipe is higher than the pipe connection for water suction try to keep the water discharge pipe as vertical as possible and the water outlet c...

Page 10: ...nical surface of the connecting nut the refrigerant oil used must be compatible with the refrigerant of this model and screw it 3 to 4 turns with your hand to tighten it as shown in the Fig 3 9 When c...

Page 11: ...ge Refer to the following table to determine the tightening torque 1 Bend the pipe or drill a hole in the wall as needed The cross sectional area of the pipe bending deformation must not exceed 1 3 of...

Page 12: ...e or valve No power cable is attached to this equipment The user can select the power cable by reference to the stipulated power supply specifications No joint of wires is allowed Upon completion of w...

Page 13: ...ng issues before trial operation and the box for the confirmed items Perform the trial run only after the outdoor unit has been powered on for over 12 hours Check that all valves are opened before tri...

Page 14: ......

Reviews: