background image

5.2 Water Discharge Test

Before the test, make sure that the water discharge pipeline is 
smooth, and check that each connection is sealed properly.
Conduct  the  water  discharge  test  in  a  new  room  before  the 
ceiling is paved.

2. Connect the power supply, and set the air conditioner to operate in
cooling  mode.  Check  the  sound  of  the  drain  pump,  and  check 
whether the drainage outlet is discharging water properly (based on 
the length of the pipe, the discharge may occur 1 minute), and check 
for water leakage at each joint.

To water suction pipe

Test water outlet

Unit

Drainage pan

Water cover assembly

Water injection pipe

Water discharge trench

Faults, if any, need to be rectified in time.

The drainage plug at the bottom of the unit is used to discharge 
accumulated  water  from  the  drainage  pan  when  the  air 
conditioner malfunctions. When the air conditioner is operating 
normally,  make  sure  the  drainage  plug  is  properly  plugged  to 
prevent water leakage.

3. Stop the air conditioner. Wait for three minutes, and then check if
there is anything unusual. If the water discharge piping layout is not 
correct, the excessive water flow will cause the alarm indicator on the 
control box to flicker. There may even be water overflowing from the 
drainage pan.
4. Continue to add water until the alarm for excessive water levels is
triggered.  Check  if  the  drain  pump  drains  water  immediately.  After 
three minutes, if the water level does not fall below the warning level, 
the unit will shut down. At this time, you need to turn off the power 
supply, and drain away the accumulated water before you can start 
up the unit normally.
5. Turn off the power supply, remove  the water, and put  the water
cover assembly back to the original place.

1. Remove  the  water  cover  assembly  to  connect  to  the  test  water
outlet, and use the water injection pipe to inject 2000 ml of water into 
the drainage pan.

Measure  the  required  length  of  the  connecting  pipe.  Make  the 

connecting  pipe  using  the  following  method  (see  the  column  Pipe 
Connection for details).

1. Connect the IDUs before the ODU.

Bend  and  arrange  pipes  carefully  without  damaging  the  pipes 

and their insulating layers.
Before tightening the flare nut, apply refrigerant  oil on  the outer 

surface at the pipe flaring position and the conical surface of the 
connecting nut (the refrigerant oil used must be compatible with 

the refrigerant of this model), and screw it 3 to 4 turns with your 
hand to tighten it as shown in the Fig 3-9.
When  connecting  or  removing  a pipe,  use  two  wrenches  at  the 
same time.
Do not put the weight of the connecting pipe on the connector of 

the IDU. Otherwise, the heavy weight will deform the  connector 
and affect the cooling (heating) effect.

Do not bend a pipe more than 90 degrees (see the figure on the 

right).
The  bend  should  be  as  close  as  possible  to  the  center  of  the 
tube  and  the  bend  radius  should  not  be  less  than  3.5D  (pipe 
diameter).
Do not bend the flexible tube back and forth more than 3 times.

When  bending  a  pipe,  cut  off  the  required  recess  in  the 
insulation pipe at the bend and expose the pipe (wrap the bend 

with a binding tie after bending).
Keep the elbow radius as much as possible to prevent flattening 

or crushing. Use a pipe bender to make tight elbows.

2. The  check  valve  of  the  ODU  should  be  completely  closed  (e.g.

the ex-factory condition). 

3. After  the  refrigerant  pipe  is  connected  to  the  IDU  and  ODU,
discharge  the  air  according  to  the  column  Air  Discharge.  After  the 

air is discharged, tighten the service nut.
Precautions for flexible pipes:

Bend a thin-walled connecting pipe (see the right figure):

Unscrew  nuts  from  the  check  valve  in  each  connection,  and 
connect the flared tube immediately (within 5 minutes). When the 

nut at the check valve is removed and placed for too long, dust 
and  other  sundries  may  enter  the  pipeline  system  and  cause 

failures at a later time. 

Fig 3-9

Apply refrigerant oil

Bend the pipe with your thumbs

connections of IDU and ODU

5.3 Connection of Connecting Pipe

Do not let air, dust, or other particles invade the pipeline system 
during installation of the connecting pipes.
Install  the  connecting  pipes  only  when  the  indoor  and  outdoor 
units are secured.
Make  sure  to  keep  the  connecting  pipes  dry  during  installation 
so that no water will enter the piping system.
Connecting  copper  pipes  must  be  wrapped  with  insulation 
materials (thicker than 10mm, the thickness should be increased 
if the unit is installed in a closed humid place).

CAUTION

Maximum 

length (m)

Maximum level 

difference (m)

Maximum number 

of bends

Notes: If the height difference is greater than the allowed level 
difference, it is recommended to place ODU above the IDU.

20

15

15

Product 

Model

53/71

30

20

15

90/105/120

50

25

15

140/160

CAUTION

CAUTION

9

Summary of Contents for OTEC IECS-D Series

Page 1: ......

Page 2: ...sconnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the nat...

Page 3: ...requirement 18 Vacuum pump Charge hose R410A special requirement 19 Torque wrench 20 Copper pipe gauge adjusting projection margin 21 Vacuum pump adapter Required tools for installation work 1 Philip...

Page 4: ...ry if the location is not strong enough Carry out the specified installation works to prevent strong winds or earthquakes Improper installation may cause the unit to drop leading to accidents Before w...

Page 5: ...ling when necessary b Adjust the position of the unit and make sure that the gap with the ceiling is evenly spaced on all four sides of the unit and the base of the unit is 10 12 mm into the base of t...

Page 6: ...therwise it may cause water to leak Calibrate the levelness of the IDU using a spirit level or polyethylene tube filled with water The IDU is equipped with a built in drain pump and float switch Do no...

Page 7: ...ook Drainage pan hook Hook screw Phillips screwdriver Swing motor Foam at panel side Unit Ceiling Panel Panel bubble 1 Air outlet Air deflector Panel bubble 2 4 6 mm The plastic cover plate protruding...

Page 8: ...outdoor unit and the indoor unit may not exceed the allowable piping length In the case that the installation place is exposed to strong wind such as a seaside make sure the fan operating properly by...

Page 9: ...from becoming loose When the outlet of the water discharge pipe is higher than the pipe connection for water suction try to keep the water discharge pipe as vertical as possible and the water outlet c...

Page 10: ...nical surface of the connecting nut the refrigerant oil used must be compatible with the refrigerant of this model and screw it 3 to 4 turns with your hand to tighten it as shown in the Fig 3 9 When c...

Page 11: ...ge Refer to the following table to determine the tightening torque 1 Bend the pipe or drill a hole in the wall as needed The cross sectional area of the pipe bending deformation must not exceed 1 3 of...

Page 12: ...e or valve No power cable is attached to this equipment The user can select the power cable by reference to the stipulated power supply specifications No joint of wires is allowed Upon completion of w...

Page 13: ...ng issues before trial operation and the box for the confirmed items Perform the trial run only after the outdoor unit has been powered on for over 12 hours Check that all valves are opened before tri...

Page 14: ......

Reviews: