background image

5    WATER DISCHARGE PIPING LAYOUT

5.1 Installation of water discharge piping for 

the IDU

Use  PVC  pipes  for  the  water  discharge  pipes  (outer  diameter: 
37–39  mm,  inner  diameter:  32  mm).  Based  on  the  actual 
installation  circumstance,  users  can  purchase  pipes  with 
appropriate length from sales agent or local after-sales service 
center, or purchase directly from the market.
Insert the water discharge pipe into the end of the water suction 
connecting pipe of the unit, and use the ring clamp (accessory) 
to clamp the water discharge pipes with the insulation casing for 
the water outlet piping securely.

Use insulation casing to evenly wrap the water suction piping 
connections and water discharge piping of the unit (especially 
the indoor portion) and bind them firmly to make sure air does 
not enter and condense to form water.
In order to prevent the back-flow of water into the interior of the 
air  conditioner  when  the  unit  stops  operating,  the  water 
discharge  pipe  should  slope  downwards  towards  the  outside 
(drainage side) at a slope of more than 1/100. Make sure that 
the  water  discharge  pipe  does  not  swell  or  store  water, 
otherwise it will cause abnormal sounds.

When connecting the water discharge piping, do not use force to 
pull the pipes to prevent the water suction pipe connections from 
coming loose. At the same time, set a supporting point at every 
0.8–1.0 m to prevent the water discharge pipes from bending.

Slope of 1/100 or more

0.8–1.0 m

> 1.0 m

Make  sure  all  the  connections  in  the  piping  system  are 
properly sealed to prevent water leakages.

When  pipe  bending  is  required,  use  water  outlet  connecting 
fittings in the junction box for pipe layout.
When  a  long  water  discharge  pipe  is  connected,  the  indoor 
portion  must  be  covered  with  insulation  casing  to  prevent  the 
long pipe from becoming loose.
When the outlet of the water discharge pipe is higher than the 
pipe  connection  for  water  suction,  try  to  keep  the  water 
discharge  pipe  as  vertical  as  possible,  and  the  water  outlet 
connecting  fittings  will  bend  so  that  the  height  of  the  water 
discharge pipe should be within 1000 mm away from the base of 
the drainage pan. Otherwise there will be excessive water flow 
when the operation stops.

The  end  of  the  water  discharge  pipe  must  be  more  than  50  mm 
above  the  ground  or from  the  base  of  the  water  discharge  slot. In 
addition, do not submerge it in water. To discharge the condensed 
water  directly  into  a  ditch,  the  water  discharge  pipe  must  bend 
upwards  to  form  a  U-shaped  water  plug  to  stop  the  odour  from 
entering the room via the water discharge pipe.

50–100 mm

200 mm

Water outlet 
pipe fittings

Main water 

outlet pipe

Slope of 
1/100 or more

200 mm

200 mm

50–100 mm

50–100 mm

Do  not  exert  too  much  force  in  order  not  to  break  the  pipes. 
Wrap  both  the  suction  piping  and  water  discharge  piping 
evenly  with  heat  insulation  casing  to  prevent  water 
condensation.

Water discharge pipes from multiple units are connected to the main 
water discharge pipe to be discharged through the sewage pipe.

>30cm

/11.81in

>

30

cm

/1

1

.8

1i

n

>

20

0c

m

/7

8.

74

in

>60cm

/23.62in

(Wall or obstacle)

Maintain channel

Air outlet

Air inlet

M

P

Air inlet

N

Fig 4.4

4.3   Space of installation and maintenance

4.4   Moving and installation

Fig 4.5

Fix with bolt

Since the gravity center of the unit is not at its physical center, 
so please be careful when lifting it with a sling.

Never  hold  the  inlet  of  the  outdoor  unit  to  prevent  it  from 
deforming.

Do not touch the fan with hands or other objects.

Do not lean it more than 45°, and do not lay it sidelong.

Make  concrete  foundation  accoding  to  the  sepecif-ications  of 
the outdoor units.

(Refer to Fig.4.5)

Fasten  the  feet  of  this  unit  with  bolts  firmly  to  prevent  it  from 
collapsing  in  case  of  earthquake  or  strong  wind.

(Refer  to 

Fig.4.6)

 

CAUTION

CAUTION

8

Summary of Contents for OTEC IECS-D Series

Page 1: ......

Page 2: ...sconnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the nat...

Page 3: ...requirement 18 Vacuum pump Charge hose R410A special requirement 19 Torque wrench 20 Copper pipe gauge adjusting projection margin 21 Vacuum pump adapter Required tools for installation work 1 Philip...

Page 4: ...ry if the location is not strong enough Carry out the specified installation works to prevent strong winds or earthquakes Improper installation may cause the unit to drop leading to accidents Before w...

Page 5: ...ling when necessary b Adjust the position of the unit and make sure that the gap with the ceiling is evenly spaced on all four sides of the unit and the base of the unit is 10 12 mm into the base of t...

Page 6: ...therwise it may cause water to leak Calibrate the levelness of the IDU using a spirit level or polyethylene tube filled with water The IDU is equipped with a built in drain pump and float switch Do no...

Page 7: ...ook Drainage pan hook Hook screw Phillips screwdriver Swing motor Foam at panel side Unit Ceiling Panel Panel bubble 1 Air outlet Air deflector Panel bubble 2 4 6 mm The plastic cover plate protruding...

Page 8: ...outdoor unit and the indoor unit may not exceed the allowable piping length In the case that the installation place is exposed to strong wind such as a seaside make sure the fan operating properly by...

Page 9: ...from becoming loose When the outlet of the water discharge pipe is higher than the pipe connection for water suction try to keep the water discharge pipe as vertical as possible and the water outlet c...

Page 10: ...nical surface of the connecting nut the refrigerant oil used must be compatible with the refrigerant of this model and screw it 3 to 4 turns with your hand to tighten it as shown in the Fig 3 9 When c...

Page 11: ...ge Refer to the following table to determine the tightening torque 1 Bend the pipe or drill a hole in the wall as needed The cross sectional area of the pipe bending deformation must not exceed 1 3 of...

Page 12: ...e or valve No power cable is attached to this equipment The user can select the power cable by reference to the stipulated power supply specifications No joint of wires is allowed Upon completion of w...

Page 13: ...ng issues before trial operation and the box for the confirmed items Perform the trial run only after the outdoor unit has been powered on for over 12 hours Check that all valves are opened before tri...

Page 14: ......

Reviews: