Output programming
The next setting of the technician menu is
«OUTPUT». Via this
setting we can program how each of the outputs
Ρ1, Ρ2 will
operate. When an output is activated we mean that it has 12V or
the relay has been activated. When an output has been
deactivated it has 0V.
If we press (*) select the output and press again the (*) key we are presented with the following
options:
«DISABLE OFF». The output does not operate
«LIKE SIREN». Activates the external siren (via the START terminal) with positive logic. It has 0V in
the idle state and 12V in alarm. By default this is how the P1 output is programmed.
«ON ALARM». It is activated when we have an alarm on the zone which has been programmed like:
ZONE WITH DELAY.
ZONE WITHOUT DELAY.
ZONE NEXT DELAY.
TAMPER
RADAR 2 PULSES.
«ON FIRE». It is activated when we have an alarm from a FIRE zone.
«ON PANIC». It is activated when we have an alarm from a PANIC zone.
«ON FAULT». It is activated when we have any fault.
«ON ARM». It is activated when the panel is armed.
«FLASH». It produces 3 short pulses during the arming of the panel and one long pulse during the
disarming. It can be connected to the FLASH or FL of the external siren.
«ON OFF MANUAL». It is activated manually by the keyboard of by a zone that has been
programmed as PG CONTROL.
«AC STATUS». It is activated in the event of an AC power supply failure.
«SUPPLY FIRE DETECTOR». It is suitable for powering smoke and heat detectors. It has a
permanent voltage of 12V which is disrupted for 5 seconds after every disarming. By default this is
how the output P2 has been programmed.
«ΟΝ SILENT ALARM». It is activated when an alarm has been issued by the SILENT zone.
Programming the general parameters of the system
The next selection in the technician menu is
«SYSTEM». Via this selection we can adjust various
parameters f the system:
«RESET DEFAULTS». Resets the panel to the factory default settings
(see page 13).
«ANNUAL CHECK DONE». Reset the annual check counter. If (*) is
pressed then the annual check notification will be shown after 365
days.
__
OUTPUT SELECTION __
P1
P2
____SYSTEM____
RESET DEFAULTS
ANNUAL CHECK DONE