«FIRE». This zone will issue an immediate alarm even if the panel is disarmed. It will also produce a
fire alarm message if a telephone dialer is installed. It can be used on zones that have smoke and
heat detectors.
«SILENT». The zone will issue an immediate silent alarm. It will activate the telephone dialler if
installed and not the sirens. It can be used in zones that have a panic button that can manually be
operate by a human that is been threatened.
«ZONE NEXT DELAY.». This zone if activated will issue an alarm signal after an exit delay plus the
additional exit delay.
«SET SECTION». When this zone is activated it will arm the whole system or a section of it. It can be
used to arm the panel via some other system such as a BMS or fire alarm system. The zone must be
connected with the close relay contact of the other system.
«UNSET SECTION». When this zone is activated it will disarm the whole system or a section of it. It
can be used to arm the panel via some other system such as a BMS or fire alarm system. The zone
must be connected with the close relay contact of the other system.
«SET UNSET SECTION.». When this zone is activated it will change the state of the panel or a
section of it from armed to disarmed and visa versa. It can be used to arm the panel via some other
system such as a BMS or fire alarm system. The zone must be connected with the close relay contact
of the other system.
«PG CONTROL». This zone for all the time that it is active will also activate the output that it controls.
«TAMPER». This zone will issue an immediate alarm even if the panel is disarmed. It can be used as
a zone for connecting the TAMPER outputs of the external siren or the other devices.
«RADAR 2 PULSES». This is a special zone setting used for avoiding false alarms. Only radars must
be connected to this zone. With the panel armed it operates with the following way:
If the panel receives the first alarm signal from the zone it waits for 5 minutes. If during this wait it
receives a second signal it issues an immediate alarm. If during the 5 minute wait a second signal is
not received then the first signal is considered to be a false alarm and is discarded.
After selecting the zone mode we must select the section (A,B,C). If we want to operate the panel as
a whole system then this selection is important.
The next setting is
«ZONE BELL». If we select YES when the panel is armed and the zone is
activated then the keyboard buzzer will sound. This function can be used for example to warn us that
the door of a store has opened by connecting its magnetic trap to this zone.
With the next selection
, «BYPASS» we select if a zone can be bypassed either manually or
automatically. By default this setting is set to YES for all zones. Select NO only for critical zones, (i.e.
zone with magnetic contact used for protecting a safe) so that the system cannot be armed when the
specific zone is active.
The
«FORCED ARM» setting has 2 different operation modes. If we select YES then if the zone
during the arm process is active (i.e. open window) the system will be armed without regarding this
zone. The zone is regarded again by the system when it stops being active ( i.e. when the window
closes). If we select NO and the zone during the arming process is active (i.e. open window) and the
automatic bypass has been selected, the system will warn us that the arming is not possible.
For the last three setting if we select ZONE MODE the panel will automatically select the correct
setting. If no special setting are require then it is good practice to not alter these.