Smoke and heat detector connections
The connection of the fire detectors must be done to a zone which has been programmed as a
«FIRE» zone. The normally closed contacts of the relay on the base (NC,C) are connected in series
with the resistor of the zone of the panel.
The power to the base is done using (-) and the output
Ρ2 which by default is programmed as «
SUPPLY FIRE DETECTOR ».
Warning:
The BS-413 and smoke detectors cannot co-exist on the P2 output. Depending on its use,
this output must be suitably programmed.
3.3 Programming via the keyboard
Let it be noted that when trying to change a setting in the user menu or the technician menu you can
view the current value of the setting. The only menus that do not offer the preview of default values
are the 2 menus
«CALL ON» on the PSTN and GSM, as well as the 2 menus «EVENTS
NOTIFICATION» of the ARC (Alarm Receiving Center) of the PSTN and the GSM.
Also when a value is entered (i.e. entry time), and after the last digit is entered the value is stored
automatically without the need to press an additional key. If we do not reach the last digit of the value
and the
„*‟ is pressed then the value that is shown on the display is stored. There is always an
indication on the display that shows which digit is edited. This is shown with the symbol
„^‟ under the
current digit. If the entered number is not within the limits then the cursors returns to the first digit.
When the adjacent display is shown the system is in the process of an
important process which cannot be stopped by using the keyboard.
The process will finish and then the display will show the main menu.
If a problem occurs during the process then a relative message will be
shown before the return to the main menu.
Sometime a menu can contain content that cannot be shown in one screen. In this case a scroll bar is
shown and we can change screens using the up and down keys. The scroll bar looks like the symbols
below:
UPDATING DATA..