Periphery Learning
In the menu item
Periphery Learning
the heating circuit regulator recognises which components (devices, pumps,
mixers and sensors) exist in the heating system. After
Periphery Learning
the Touch operating device indicates, if all
components are present.
Note
All heating controllers, burner controller, touch operating devices and remote controls must be addressed and
turned on.
Periphery Learning
is in the Main menu.
Periphery Learning
appears only in the level for the
ÖkoFEN service technician.
Confirm the query.
Note
After this query it is not possible to get back.
•
Cascade - number of boilers
Enter the number of existing boilers.
Note
If the number of boilers is higher than 1,
additional settings are necessary. See
26.1
Cascade settings, page 68
•
DHW - Switch On/Off - sensor
Choose a Switch On and a Switch Off sensor.
Note
Appears only if a accumulator exists in the
system.
•
Allocation
Assign Heating circuit 1-6 and DHW 1-3 to the
respective boiler or accumulator.
• Touch the Button
Periphery Learning
.
The heating circuit controller examines and
recognises the existing components.