Heating circuits settings

56

Flow range

This function dynamically reduces the rate at which the mixer operates to reduce
boiler cycling, particularly useful when starting systems with high load.

Boiler temperature
smoothing

The boiler temperature smoothing controls the boiler load by smoothing the operation
of the mixer.

Note

The boiler temperature smoothing operates only on systems

without

accumulator and existing boiler.

Temperature rise

The minimum value of the temperature rise at the boiler sensor.

Boiler load control range

Is the temperature range within the Pelletronic measures.

Minimum Temp/Rise time

This is the minimum temperature rise required over the rise time.

1

The boiler temperature rises or exceeds the minimum temperature within the set

rise time.
The Mixer opening time is not influenced.

2

The boiler temperature remains steady within the set rise time.

The mixer stays in the same position.

3

The boiler temperature falls within the set rise time.

The mixer starts to close.

4

The boiler temperature rises or exceeds the minimum temperature within the set

rise time.
The Mixer opening time is not influenced.

Operating manual Pelletronic Touch

E1389EN 2.0

Summary of Contents for PELLETRONIC TOUCH

Page 1: ...Operating Manual PELLETRONIC TOUCH TOUCH V2 00 ENGLISH Europe s specialist in pellet heating E1389EN 2 0 ...

Page 2: ...13 Approved Humberger Stephan Author ÖkoFEN Forschungs und EntwicklungsgesmbH Technical editorial department Gewerbepark 1 A 4133 Niederkappel AUSTRIA Tel 0043 0 7286 7450 Fax 0043 0 7286 7450 10 oekofen pelletsheizung at www oekofen com by ÖkoFEN Forschungs und EntwicklungsgesmbH Subject to modifications ...

Page 3: ...ring values Solar 29 10 2 Solar circuit 30 10 3 Yield Solar Energy 31 11 Pellematic 32 11 1 Permanent operation 32 11 2 Measuring values Pellematic 33 11 3 Full Power 34 11 4 De ashing system 34 11 5 Fresh Water Module 35 11 6 Boiler Cleaning 35 11 7 Suction System 36 11 8 Level detection system 37 12 Heat Main Pump 38 13 General 39 13 1 Favorite 1 and 2 39 13 2 Local Settings 40 13 3 Malfunction ...

Page 4: ...easuring values 73 27 2 Ignition settings 73 27 3 Full power settings 74 27 4 Run On Time settings 75 27 5 Output Settings 76 27 6 De ashing system settings 76 27 7 Boiler cleaning 77 27 8 Washing 78 27 9 Settings 79 27 10 Boiler Controlled Pump 80 27 11 FRT Controller 81 27 12 Negative Draft 82 28 Heating Main Pump 83 29 General settings 84 29 1 Sensor Adjust 84 29 2 Output Test 85 29 3 Factory s...

Page 5: ...ed with this unit in a safe place for future reference Please pass on the documentation to the new user if you decide to part with the unit at a later date Please contact your authorised dealer if you have any questions ÖkoFEN attaches great importance to the development of new products Our R D Department repeatedly challenges the effectiveness of tried and tested systems and works continuously on...

Page 6: ...es regulations and standards as part of the declaration of conformity that applies to this type of equipment EU guidelines Designation 2006 42 EG Guidelines for machines 2006 95 EG Low voltage guidelines 2001 95 EG Product safety guideline 2004 108 EG Guideline for electromagnetic compatibility of components EMVG The following harmonised standards have been applied Standards Designation EN 303 5 B...

Page 7: ... to death or life threatening injury Warning indicates a situation that could lead life threatening or serious injury Caution indicates a situation that could lead to injury Note indicates a situation that could lead to property damage 2 Consequences of risk Effects and consequences resulting from incorrect operation 3 Avoiding risk Observing safety instructions ensures that the heating system is ...

Page 8: ...ll menu options and measuring values of the heating controller All specific settings of the heating system is done with the Touch operating device 4 1 Operating Device with Touch screen The Touch operating device is mounted on the control board of Pellematic The 4 7 color display is surrounded by a design foil with logo Apply finger pressure to operate the Touch screen 4 2 Opening window The touch...

Page 9: ...for exhaust gas measurement Menu Chimney sweep is in the opening window After selecting the chimney sweep function it will query whether to execute If yes then press the tick box Boiler temperature set is 60 C for the total running time of 30 minutes It displays the actual boiler temperature and delay time Chimney sweep is stopped with Cancel E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 10: ...n With the blue up arrow you get to additional lines of information on this item Top of page scroll up Navigate to the respective menu item Once the respective item has been selected then parameters may be set It will display either a numeric or text keypad 2 Numeric keyboard a Name of parameter b Value of parameter with unit c Min max value Values outside this range are not accepted d Delete inpu...

Page 11: ...inus block you change numbers 4 Text selection a Name of parameter b Status texts The number of status texts depends on the parameter Choose a status text The setup menu closes automatically and the chosen status text is displayed in the menu Note Although a scroll down menu is open the navigation parameter icons behind are still active and can be used E1389EN 2 0 Operating manual Pelletronic Touc...

Page 12: ...and operating device with touch screen 12 4 5 Main Menu In the main menu all submenus are displayed Press the icon required to access that programme Menu navigation of Pelletronic Touch Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 13: ...The adjusted operating mode of the heating circuits and DHW is inactive The frost protection function is active Auto The adjusted operating mode of the heating circuits and DHW is active The frost protection function is active Domestic hot water The adjusted operating mode of the DHW is active The adjusted operating mode of the heating circuits is active The frost protection function is active The...

Page 14: ...g circuits in your heating system In the menu item Domestic hot water you see all actual and set values of the DHW production In the menu item Solar you see all actual and set values of the solar thermal system In the menu item Accumulator you see all actual and set values of the accumulator In the menu item System you see all actual and set values of the overall heating system In the menu item Al...

Page 15: ...Measuring Values 15 System Status is an overview of the whole heating system E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 16: ...m temperature Heating The boiler heats constantly accordingly to the Set room temperature Set back The boiler heats constantly accordingly to the Set back room temperature The operating mode of the heating circuits can only be changed if the plant operating mode is set to AUTO The adjusted heating limits and maximum flow temperatures are used in all operating modes Room Temp Heating Choose your ro...

Page 17: ... heating times Time 1 Timeprogramme 1 and Time 2 are in the menu Heating circuit 1 Select Time programme 1 6 Mo Fr were assigned heating times With you get to the remaining days Sa Su 2 Select the heating days The activated days are displayed in green 7 Sa Su were assigned to heating times 3 Enter the heating times for these heating days Mo Th 8 With and you switch between the heating blocks You c...

Page 18: ...et all the heating times in the line and below to 0 5 Friday is activated and heating times assigned 10 Go back with Select Time 2 For each circuit are two time programmes You can select two time programs In the menu item Time Allocation you can activate Time programme 1 or 2 Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 19: ... the party function deactivates itself automatically 7 4 Vacation The holiday programme cancels the heating times and heats for the entered period on the set temperature level Vacation is in the Main menu Enter the room temperature on which in your absence the building should be heated Enter the departure start time and return finish date and activate the vacation programme Note To return to an al...

Page 20: ...rcuit Heating curve 0 0 4 0 The heating curve describes the combination between outdoor temperature and the associated flow temperature for a heating circuit Base point adjustable from 20 45 With the change the of base point you provide a parallel shift of the heating curve H limit heating If the average outside temperature is higher than the set temperature the heating circuit switches off in the...

Page 21: ...han one adjustment step per day Room temperature Daytime outside temp too warm too cold Decrease heating curving value by 0 2 Increase heating curving value by 0 2 5 to 15 C Decrease base point value by 5 Increase base point value by 5 20 to 5 C Decrease heating curve value by 0 2 Increase heating curve value by 0 2 E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 22: ... If the measured room temperature deviates from the set room temperature it corrects the heating controller and the flow temperature with the room thermostat influence The Room thermostat influence indicates how much the flow temperature is raised or lowered so that the Set room temperature is reached Room temperature hysteresis The room temperature hysteresis prevents the cycling On Off On Off of...

Page 23: ...Heating Circuit 23 E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 24: ...emperature for the conditions of the floor No libility is accepted by the Pelletronic supplier for damage to floors or sub floors Continuous power supply is required to the controller to maintain the settings for this programme Only use programme temperatures approved by the UFCH and flooring suppliers Screed programme is in the menu Heating circuit At the end of the screed programme it will switc...

Page 25: ...the Water temp set You can change the mode domestic hot water only when the Operation mode is on AUTO DHW Boost Heats the hot water once on the Water temp set Water Temp Set Set the water temperature Water Temp Min Set the minimum water temperature The water temperature never falls below this value unless the domestic hot water mode is OFF Values You see all the DHW corresponding measuring values ...

Page 26: ...nsores Outputs pumps mixer and motors 8 2 Time programme DHW In the Time Programme DHW return pump you set the DHW usage times Time 1 Time programme 1 and Time 2 are in the menu Domestic hot water The domestic hot water time programme works the same way as the heating circuit time programme See chapter 7 2 Time programme Heating circuit page 17 Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 27: ...n temperature falls below the switch off temperature the DHW Return pump switches on again Time Allocation Choose the time programme 1 or 2 Values You see all the DHW pump corresponding measuring values Time 1 Time 2 In the Return pump time programme you set the run times of the Return pump The Return pump time programme works the same way like the heating circuit time programme See chapter 7 2 Ti...

Page 28: ...mp you set the DHW usage times Time 1 Time programme 1 and Time 2 are in the menu DHW return pump The DHW return pump time programme works the same way as the heating circuit time programme See chapter 7 2 Time programme Heating circuit page 17 Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 29: ...r is in the Main menu Solar has following menu items Measuring values Solar Solar circuit 1 2 Solar energy Yield 10 1 Measuring values Solar Measuring values Solar is in the menu Solar It displays all measuring values of Solar Actual values Set values Inputs sensors Outputs pumps mixer and motors E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 30: ...he ACC temp Max is reached The temperature must fall under ACC temp Max minus hysteresis then the solar circuit pump switches on again The hysteresis prevents a solar pump cycling On Off On Off Collector Hyst On If between the collector sensor and TPU ACC lower sensor the temperature difference is greater than the Coll Hyst A switches the solar pump On Collector Hyst Off If between the collector s...

Page 31: ...e menu Solar Yield measuring of solar energy has following menu items Actual Display of the current solar energy refreshes every 60 sec Yield Day Display of todays solar energy since 00 00 Yield Day before Display of the of yesterdays solar energy Yield since Display of the solar energy since the last set date Flow rate Display of the current flow rate refreshes every 60 sec Flow temperature Displ...

Page 32: ...ning Pellet level 11 1 Permanent operation Permanent operation is in the menu Pellematic If you confirm the query you acitvate the function Permanent operation First of all the spring driven motor opens the fire protection system at the burner the process takes about 2 minutes After that the burner motor runs in permanent operation and transports pellets to the burner plate In heating systems with...

Page 33: ...percent UW Speed Power of the pump with activated speed control Burner Contact Status On Off Kap RA Capacitive sensor of the burner Status On Off Kap ZW Capacitive sensor at the hopper Status On Off Note Default display always with suction system Display alternative with auger system Flame Return Gate Status On Off Flame Return Gate Existing Boiler Status On Off Existing Boiler Ignition Temperatur...

Page 34: ...setpoint temperature The burner motor is controlled accordingly You can reduce or increase the value calculated by the PLC 10 steps up or down 11 4 De ashing system De ashing system is in the menu Pellematic The menu item De ashing system is available only when De ashing system is connected The activation is only possilbe after entering the Code for service tecnicians The de ashing system and the ...

Page 35: ... the same time regardless of whether it is empty or not Cleaning 2 You can set in Cleaning Filling a second cleaning sequence The value to be set is the time full hour at which the additonal boiler cleaning sequence is performed Example 20h additional boiler cleaning sequence performed at 20 00 On vacuum systems the hopper is also filled at the same time regardless of whether it is empty or not De...

Page 36: ...be set The value to be set is the time full hour at which the additonal boiler cleaning sequence is performed Example 20h additional boiler cleaning sequence performed at 20 00 On vacuum systems the hopper is also filled at the same time regardless of whether it is empty or not Frequ RA Motor Frequency for storage room suction systems in pulse mode only for vacuum systems Pause RA Motor Pause time...

Page 37: ...em using weighing cells at the hopper for storage rooms only for Pellematic Type PES 36 56 Capacitive Sensor Level detection system using a capacitive sensor for storage rooms and Textile tanks Limit Value is the minimum weight for a warning message Value adjustable The warning message appears on the operating device and disappears when the filling weight is above the set minimum weight Mode Choos...

Page 38: ...n the menu item Component you can assign any or all circuits to operate with the Heat Main Pump The Heat Main Pump runs with any assigned pump Switch the Heat Main Pump On or Off Note For each heating controller only one Heat Main Pump or circulation pump can be used The Heat Main Pump and the circulation pump are closed from each other Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 39: ... Local setting Malfunction Info 13 1 Favorite 1 and 2 Favorite is in the General menu With this function you can display most commonly used menu items in the start menu This then enables direct access Select the menu item you wish to be displayed as Favorite 1 in the Start menu The selected item is now green this icon is now displayed in the start menu and active E1389EN 2 0 Operating manual Pelle...

Page 40: ...tems Language Unit Date Time Language Choose between the languages German English UK English U S French Spanish Italian Dutch Danish and Russian Unit You can choose between metric and imperial measuring systems Date Set the current date Time Set the current time Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 41: ...l remain until acknowledged The fault remains in the incident reports log until corrected 13 4 Information Information is in the General menu In the menu item Information all faults are listed chronologically The fault texts have 3 status C CURRENT when the fault occurs Q QUIT when the fault has been rectified G GONE when the fault has been reset by pressing ENTER E1389EN 2 0 Operating manual Pell...

Page 42: ...Software 42 14 Software Software is in the Main menu Software shows the current version of software in use Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 43: ...ced settings for startup and customisation of the heating systems are possible The service technician level is protected with a password code to prevent unauthorised changes The password code entry appears in the main menu Code Input is in the Main menu Touch the icon Code input Enter the code in the numeric block You have reached the level of ÖkoFEN service technicians All additional menu items a...

Page 44: ...rised personnel Before performing start up on the installation you must consider using the checklist for the entire heating system see Pellematic installation instructions To perform the installation specific settings you must enter via code input into the service technician level See Chapter 15 Code Input page 43 Menu guide shows the menu levels and menu items of the Pelletronic heating controlle...

Page 45: ...heating controller is protected up to 8A total current consumption Each output may be occupied with 2 A Make sure that these values are not exceeded by the connected devices 1 Bus connecting terminal RS485 A and B 5 Fuse 8 A slow acting limits the current consumption of the heating controller 2 Address switch 6 Low voltage area dangerous voltage 3 Slot for an optional power supply The power supply...

Page 46: ... heating controllers you assign each heating circuit starting with 0 for the corresponding number 0 2 0 Heating controller 1 1 Heating controller 2 2 Heating controller 3 Property damage Adjust the order by using the address switch this is only possible if the heating system is powered down Note The settings in the remote control are described in the Operation instruction Remote controller Operati...

Page 47: ...ess switch If operating as a cascade system set the switch accordingly Base setting 0 At the operating with cascade systems you assign to every boiler with 0 beginning the suitable number Property damage Adjust the order using the address switch this is only possible when the system is powered down E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 48: ...1 to 4 must be inserted at the input RGF 10 11 terminal of each boiler controller before using Learn Periphery The different Pellematic plugs 1 to 4 must be numbered according to the boiler numbers Property damage Adjust the order using the address switch this is only possible when the system is powered down Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 49: ...Description of the heating controller module 49 17 4 Assembly or disassembly of the power supply E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 50: ...amage to the insulation board by electrostatic charging 2 Open the cover plate of the heating controller See previous chapter 17 4 Assembly or disassembly of the power supply page 49 3 Pull all the plugs in from the circuit board Leave the plugs with the wiring in the casing 4 Disassemble of the power supply optional See previous chapter 17 4 Assembly or disassembly of the power supply page 49 5 D...

Page 51: ...lows Electric shock Switch off the system before work commences on the boiler Breakdown Touch operating device Before you press out the Touch operating device you must unplug all cables from the operating device While pressing out the operating device you have to counter the top with the palm so that the operating device does not pop out and fall to ground E1389EN 2 0 Operating manual Pelletronic ...

Page 52: ...gured as Master and one as Slave per heating system Procedure 1 Choose menu item Software Touch Configuration 2 Choose for each Remote control the Configuration Slave and assign it to a heating circuit 3 Wait until all components are booted up and operational 4 Learn Periphery See capitel 20 Periphery Learning page 54 5 The Operating device and the associated Remote controller are functional now 1...

Page 53: ...evice in the control panel 5 Switch on the heating controller 6 Go to the CODE button enter the code to reach the level settings 7 Go to the button Software 8 Choose Update Note If you have forgotten to insert the USB stick Press the Refresh button wait about 1min 9 Select the appropriate software 10 Press the Button Update and reply to the query with YES 19 4 Software Update First perform a softw...

Page 54: ...rs only in the level for the ÖkoFEN service technician Confirm the query Note After this query it is not possible to get back Cascade number of boilers Enter the number of existing boilers Note If the number of boilers is higher than 1 additional settings are necessary See 26 1 Cascade settings page 68 DHW Switch On Off sensor Choose a Switch On and a Switch Off sensor Note Appears only if a accum...

Page 55: ... heating circuit Min Flow temperature Set the minimum flow temperature to the chosen heating circuit Temperature increase System heat loss adjustment Set the boiler or accumulator temperature above the set flow temperature of the circuit calling for the highest temperature E g Set at 5 C with a heating DHW circuit with a set temperature of 60 C the minimum boiler accumulator temperature will be se...

Page 56: ...t the boiler sensor Boiler load control range Is the temperature range within the Pelletronic measures Minimum Temp Rise time This is the minimum temperature rise required over the rise time 1 The boiler temperature rises or exceeds the minimum temperature within the set rise time The Mixer opening time is not influenced 2 The boiler temperature remains steady within the set rise time The mixer st...

Page 57: ...l operate in parallel Temperature increase This increases the DHW set temperature E g Use this function to over come heat losses in connecting pipe work Pump run on This function is set in minutes and determines the run on time of the DHW pump This allows residual energy in the boiler or accumulator to be transferred to the DHW cylinder E g 10 min or if the boiler temp is lower than DHW cylinder w...

Page 58: ...ion may not be possible in some types of cylinder due to position of boiler coil or other considerations consult relevant cylinder manufactures for details Risk of Scolding from very hot water Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 59: ...They are present after entering the code Pump release temperature The DHW temperature must be higher than the Pump release temperature otherwise the DHW return pump does not switch on Flushing interval If the DHW Return Pump is not active although it is in the ON mode the pump runs according to the Flushing interval for refreshing the return flow sensor Purging time Enter the Flushing time min whi...

Page 60: ...nus Coll Overheating Hyst temperature Pump Diverter Valve You can choose for every solar circuit between solar pump and diverter valve Pump Type Choose between A category pump and standard pump Pump Speed Controller The speed regulation of the solar pump can be switched on and or off Only functions with suitable pumps If the pump speed control is on standard pumps can be damaged D2 different types...

Page 61: ...ime you set the scavenging interval Scavenging Collector Temp Min If the collector temperature is below the collector temperature minimum the scavenging process is not performed Scavenging Start Time Scavenging Stop Time With the Start Time you set the beginning of the scavenging process Start and Stop time are avoiding an unnecessary operation of the solar circuit pump Prio Mode Systems with more...

Page 62: ...erence between collector and TPU lower sensor from the solar circuit with PRIO A is higher than the temperature difference both solar circuits run parallel The parameter value is only in solar circuits with PRIO A visible and adjustable Timing chart for 2 solar circuits with 1 pump and 1 diverter Valve and 2 solar circuits with 2 pumps solar circuit 1 Prio 1 solar circuit 2 Prio 2 Operating manual...

Page 63: ...the flow rate The basic setting 1 0 l min corresponds to the flow rate of the ÖkoFEN profit set Delete Delete the date and the gain of Gain since Note Remove the date and the actual gain during the startup by pressing the Delete button E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 64: ...mp On Temp If the temperature at the TPO AC upper sensor rises over the value of the Pump On Temp all the pumps of the assigned participants are activated Pump Depends on Require ON The accumulator is loaded the accumulator is not loaded further OFF The accumulator is loaded but the accumulator is charged further as long as the accumulator temperature does not exceed the accumulator temperature or...

Page 65: ...Accumulator settings 65 E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 66: ...the Boiler Temperature Max all heating circuit pumps switch on to transport the heat energy out of the boiler This process stops when the boiler temperature falls below the Boiler Temperature Max Boiler Temp Above e G BT Max 95 C minus Boiler Temp Above 10 C 85 C Frost Protection Protection Temp If the outside temperature falls below the Frost Protection Protection Temp the heating circuits are sc...

Page 67: ...System Controlling 67 Outside Temperature Time of Average With this function you define how long the outside temperature should be determined 0 no message E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 68: ... possible with accumulator No 1 If accumulator No 1 is installed all boilers must be assigned to this accumulator No 1 The accumulator pump must be connected to the boiler Periphery Learning Note Prior to the Periphery Learning all components must be connected properly The number of boilers and selection of the switch off sensor in a cascade system with an accumulator must be taken in the menu Per...

Page 69: ... there is an individually adjustable Hysteresis The Hysteresis enables a gradual ON and turn OFF of the boilers See graphic Delay Time The setting of the Delay Time refers to the starting numbers of the boilers Apart from the starting number 1 each starting number has a Delay Time At first it starts only the boiler with the starting number 1 Every other boiler starts at the end of the Delay Time i...

Page 70: ...System Controlling 70 Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 71: ...regulated by the Pelletronic Touch Pump On Temp Replace with If the Boiler temperature reaches the Pump On Temp the pumps are switched on Switch Temp If the Switch Temp is reached the Pellematic switches off The switch valve stays to use the residual heat of the Pellematic Temp Max If the existing boiler reaches the Temperature Max outside the heating times all DHW circuits and heating circuits sw...

Page 72: ...he Pellematic switches off The system draws the energy further from the Pellematic until the Existing Boiler reaches the Pump On Temp Only then the energy from the Existing Boiler is obtained Advantages The available energy of the Pellematic is used as much as possible The condensation of the Existing Boiler is prevented Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 73: ...an Flue Gas Fan Hyst Flue Gas Temp Min Flue Gas Temp Max Flue Gas Temp The additional menu items Ignition settings are for the ÖkoFEN Service technician They are present after entering the code Burner Auger Run Time Run duration of the burner auger during the ignition period expressed in tenths seconds Rest Time Rest Time of the burner auger during the ignition period expressed in tenths seconds B...

Page 74: ...EN Service technician They are present after entering the code Fuel Adjustment The run duration of the burner auger is calculated from the boiler controller It is independent from the rated power and the boiler set temperature and is set automatically The burner motor is then controlled accordingly You can raise or reduce the run time calculated by the boiler controller respective in 10 steps Deli...

Page 75: ... time of the flue gas fan at the moment of switch off in seconds Burner Fan AGT Off The burner fan runs after the minimum delay time has elapsed even until the flue gas temperature is lower than the boiler temperature the set temperature value e g Boiler temperature 76 C 32 C 108 C Switch off temperature Flue Gas Fan AGT Off The flue gas fan runs after the minimum delay time until the flue gas tem...

Page 76: ...ows remote verification of pumps and valve settings Exception Accumulator pump controlled by the boiler For each connected motor you will see the following values mA actual volt actual mA minimum set mA maximum set operating hours Length of time in which the motor shall be located beyond the min and max values before an error message is displayed The min and max values and the duration are adjusta...

Page 77: ...ate cleaning system are active for 20 seconds Note If there is no burner demand longer than 5 days the de ashing system activates itself on Friday on 12 00 for 3 5 minutes This prevents a ash solidification around the auger MInimum Run Time Is the Minimum Run Time of the boiler until the next ash removal sequence Value adjustable Delivery Duration Is the run time of the ash auger Value adjustable ...

Page 78: ...hing function according to your requirements Mode Activate the washing function ON OFF Note After Learning Periphery in systems with condensing technology the mode is ON by default Min Run Time Minimum Run Time of the boiler until the next cleaning Washing Time Duration of boiler cleaning in seconds Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 79: ...n auger systems Burner Demand Choose between 2 types of regulating the burner Standard Boiler runs in accordance with the burner demand of the heating controller Impuls Boiler starts when the heating controller sends a one time signal and switches off when the Switch Off Temperature is reached Malfunction Mode If a malfunction occurs the boiler controller controls the relay fault signal The potent...

Page 80: ... menu items Boiler Controlled Pump are for the ÖkoFEN Service technician They are present after entering the code On Temp When reaching the On Temp the output UW is activated or switched on the Boiler Controlled Pump The On Temp is the boiler temperature minimum Depends On Require When reaching the On Temp and an existence of Depends On Require the output UW is activated The burner run on time is ...

Page 81: ...s the combustion chamber temperature minimum for a successful ignition Set Value Set Value for the regulation of the combustion chamber temperature Limit Up If the combustion chamber temperature falls below the Set Value increases the run time of the burner auger maximum of this percentage Limit Down If the combustion chamber temperature raises above the Set Value decreases the run time of the bur...

Page 82: ...low and for longer than 1 minute the system goes into Malfunction Value 0 the Negative Draft control is inactive Displayed only with connected Negative Draft measuring Maximum If the negative draft Maximum in the combustion chamber is exceeded for longer than 1 minute the system goes into Malfunction Displayed only with connected Negative Draft measuring Washing The function Washing is only availa...

Page 83: ... menu Each heating controller there is a maximum of one heat main pump possible You switch the Heating Main Pump ON and OFF The Heating Main Pump is a backup pump You assign the pump to all available pumps in the system When you click on an icon it lights up green A green icon symbolises an assigned pump Note A Heating Main Pump and a Return Pump exclude themselves E1389EN 2 0 Operating manual Pel...

Page 84: ...tting Sensor Adjust Output Test Factory Setting Malfunction Information USB 29 1 Sensor Adjust Sensor Adjust is in the menu General Settings For long cable lengths are slight variations of the sensor values possible The Sensor Adjust function allows you to adjust each sensor by plus minus 10 C Note You have to connect each sensor to the heating controller and activate it in the menu item Periphery...

Page 85: ...er control Output Test Pelletronic You find all the heating controller connected devices You can switch each device on and off Output Test Pellematic You find all the boiler control connected devices You can switch each device on and off 29 3 Factory setting Factory setting ist in the menu General settings You can restore the original factory settings E1389EN 2 0 Operating manual Pelletronic Touch...

Page 86: ...have plugged in USB stick Save Used to ensure the individual settings on site before you make any software updates With the file name which you enter here you can access the data when loading settings again Load Load the saved settings after a software update Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 87: ...ix 87 30 Appendix 30 1 Calibration Execute a calibration as follows 1 Switch off the whole heating system 2 Press by using a finger on the Touch operating device E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 88: ...dix 88 3 Keep your finger pressed and switch the boiler on again 4 After a few seconds of waiting time the following mask appears on the Touch operating device Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 89: ...ion Do not place items on the Touch operating device 30 2 Connection plan The Connection plan is a description of all the electrical connections from the Pelletronic heating controller Only an authorised technician may perform the electrical installation of the heating controller Make sure the whole system is powered down and isolated before commencing work E1389EN 2 0 Operating manual Pelletronic...

Page 90: ...circuit pump HK1 X26 X7 AC upper sensor PO Heating circuit pump HK2 X27 X8 AC middle sensor PM Solar pump 2 Sol P2 X28 X9 AC lower sensor 1 SPU1 Return pump Heat main pump ZP X29 X10 AC lower sensor 2 SPU2 Domestic hot water WW X30 X11 Analogue voltage output OUT1 Solar pump 1 Sol P1 X31 X12 Reserve S3 Accumulator pump PLP X32 X13 Reserve S2 Power supply 115V 240V X33 X14 Return sensor ZIRK X15 Co...

Page 91: ...SPU1 X19 Flow rate 24V Z_IN X10 AC lower sensor 2 SPU2 X20 Reserve 0 10V X11 Analogue voltage output OUT1 X21 Analogue voltage output OUT2 X34 Jumper Terminals low voltage zone X32 Accumulator pump PLP X31 Solar pump 1 Sol P1 X30 Domestic hot water WW X25 23 N Mixer HK2 closing M2 X33 Power supply 115V 240V X25 13 N Mixer HK2 opening M2 X29 Return pump Heat main pump ZP X24 Burner demand 2 BRanf 2...

Page 92: ...Appendix 92 Electrical wiring diagrams heating controller The wiring diagrams are also located on the inside of cover of the heating controller Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 93: ...with 1 Boiler controller CMP 6 2 1 Heating Controller Pelletronic 1 Touch Operating device Master 1 Touch remote control Slave Input cmp Input Touch Bus terminal WR2 Bus terminal X1 24V 1 GND GND A 2 B 3 E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 94: ...er controller CMP 6 2 2 Heating Controller Pelletronic 1 Touch Operating device Master 4 Touch remote control Slave Input cmp Input Touch Bus terminal WR2 Bus terminal X1 24V 1 GND GND A 2 B 3 Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 95: ...X1B LS YYCVY 0Z 4x0 75 x Analogue voltage output OUT1 K 28 X11 YML 2x0 75 x Analogue voltage output OUT2 K 71 X21 YML 2x0 75 x INPUTS see on wiring diagram on the front side Function Shortcut Cable Pin I O BOX Cable type Section Max Ampere Outdor sensor AF K 09 X2 YML 2x0 75 KTY 2k Boiler sensor KF K 04 X3 YML 2x0 75 KTY 2k Flow sensor HK1 VL1 K 10 X4 YML 2x0 75 KTY 2k Flow sensor HK2 VL2 K 11 X5 ...

Page 96: ...diagrams 30 5 1 Diagram 1 1 Boiler Pellematic 1 Accumulator Pellaqua 2 Heating circuits 1 Solar circuit 30 5 2 Diagram 2 1 Boiler Pellematic 1 DHW Accumulator 2 Heating circuits 1 Solar circuit Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 97: ...atic 1 Accumulator 2 Heating circuits 1 Fresh water module 1 Solar circuit 30 5 4 Diagram 4 1 Boiler Pellematic 1 Accumulator 1 Fresh water module 4 Heating circuits 1 Solar circuit 1 DHW Accumulator E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 98: ...er Pellematic 2 Accumulators 1 Fresh water module 4 Heating circuits 1 Solar circuit 30 5 6 Diagram 6 1 Boiler Pellematic 1 Accumulator 1 DHW Accumulator 2 Heating circuits 2 Solar circuits Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 99: ... 5 7 Diagram 7 1 Boiler Pellematic 1 Accumulator 2 Heating circuits 1 Layer charge module 30 5 8 Diagram 8 2 Boilers Pellematic 1 Hydraulic separator 4 Heating circuits E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 100: ...0 30 5 9 Diagram 9 2 Boilers Pellematic 1 Accumulator 1 Fresh water module 2 Heating circuits 30 5 10 Diagram 10 4 Boilers Pellematic 1 Accumulator 2 Heating circuits Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 101: ...am 11 1 Boiler Pellematic 1 Accumulator 4 Heating circuits 30 5 12 Diagram 12 1 Boiler Pellematic 1 Wooden boiler 1 DHW Accumulator 1 Accumulator 2 Heating circuits 2 Solar circuits E1389EN 2 0 Operating manual Pelletronic Touch ...

Page 102: ...Appendix 102 30 5 13 Diagram 13 1 Boiler Pellematic 1 Wooden boiler 1 DHW Accumulator 2 Heating circuits 1 Solar circuit Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 103: ...acation time OFF Temperature 15 C from act Date Time till act Date Time Heating curve Heating limits Heating curve 0 4 Base point 20 0 C H limit heating 18 0 C H limit set temperature minus 5 C Derivative time 180 min Room thermostat influence 1 Room thermostat hysteresis 0 0 C Settings Maximum flow temperature 55 0 C Minimum flow temperature 20 0 C Temperature of boiler above heating circuits 5 0...

Page 104: ... 00 00 00 00 00 00 00 00 Settings DHW preference ON Temperature of boiler above heating circuits 10 0 C Run on time 10 min DHC hysteresis 5 0 C Legionella protection Monday Accumulator PU 1 PU 2 PU 3 Settings Accumulator Temp min ON 10 0 C Pump release temperature 20 0 C Pump Depends on Require ON Pump Speed Controller OFF Pump Switch Off Hyst 3K Pump Run On Time 15min Pump Control Range 5K Solar ...

Page 105: ...0 0 C Scavenging OFF Rest time SV 10 min Run time SV 1 min Coll min SV 20 0 C Period Scavenging 09 00 18 00 Priority x Run time x Rest time x Scavenging time x Solar energy Volume per pulse 1 0 l Heat main pump Operating mode OFF Member NO System Controlling Settings Boiler Temp Above 10 0 C Boiler temperature minimum 60 0 C System Max 95 0 C Boiler Pump On Temp 60 C Outside Temperature Time of Av...

Page 106: ...rding interval 1 min Sensor calibration Sensor all sensors 0 0 C Existing boiler Valve switch on temperature 60 0 C Valve hysteresis 2 0 C Inversion UV NO Delay time 30 min Pump switch on temperature 60 0 C Operating manual Pelletronic Touch E1389EN 2 0 ...

Page 107: ......

Page 108: ...43 0 7286 7450 10 oekofen pelletsheizung at www oekofen com United Kingdom Organic Energy Ltd Severn Road Welshpool Powys Wales SY21 7AZ Tel 0044 0 845 458 4076 or 0044 0 1938 530 070 Fax 0044 0 1938 559 222 info organicenergy co uk www organicenergy co uk by ÖkoFEN Forschungs und EntwicklungsgesmbH Subject to modifications ...

Reviews: