Pellematic settings
79
27.9 Settings
Settings
is in the Pellematic menu.
Settings
has following menu items.
• Control Temperature
• Switch Off Temp
• AGT Minimum
• Delivery System Delay
• Burner Demand
• Malfunction Mode
• Hand Filling Hopper
• Capacitive Sensor RA Active
• Capacitive Sensor ZW Active
The additional menu items
Settings
are for the ÖkoFEN Service technician. They are present after entering the code:
Control Temperature
Setting the boiler temperature set.
Switch Off Temp
Reaching the Switch Off Temp, the boiler switches off.
AGT Minimum
AGT Minimum is to regulate of the boiler performance.
If the Flue gas minimum temperature falls below, the boiler power increases
independently of the boiler temperature,
Displayed only with connected flue gas sensor.
Delivery System Delay
Delay of the Delivery System relative to the burner auger – only on auger systems.
Burner Demand
Choose between 2 types of regulating the burner:
Standard: Boiler runs in accordance with the burner demand of the heating controller.
Impuls: Boiler starts when the heating controller sends a one-time signal and
switches off when the Switch Off Temperature is reached.
Malfunction Mode
If a malfunction occurs, the boiler controller controls the relay fault signal.
The potential-free contact (Output SM 20 19) displays the malfunctions by using an
external display device. (1–230V). You can choose the following functions:
On / Off:
By warning
Ash
or warning
Pellets
the contact closes
1x:
If a malfunction occurs, the contact closes – Closed
By warning "Ash box full" appears a flashing pulse. (Contact closes once)
blinc:
1 Pulse = all other malfunctions
2 Pulses = one sensor is defect
3 Pulses = one motor is defect
4 Pulses = Safety temperature sensor or emergency stop switch is defect.
Hand Filling Hopper
Setting, if Pellematic is installed as a Hand filling hopper.
0 = inactive, 1 = active
E1389EN 2.0
Operating manual Pelletronic Touch