Heating Circuit
20
7.5 Heating curve and Heating limits
Starting up for the first time, the authorised technical adviser adjusts the heating curve, the base point and the heating
limits on the building situation and the hydraulics. If the Set room temperature is not reached or exceeded, adjust the
heat curve with the flow temperatures according to outside temperatures.
Heating curve
is in the menu
Heating circuit
.
Heating curve
0.0 – 4,0
The heating curve describes the combination
between outdoor temperature and the associated flow
temperature for a heating circuit.
Base point
adjustable from 20 - 45
With the change the of base point, you provide a
parallel shift of the heating curve.
H limit heating
If the average outside temperature is higher than the
set temperature, the heating circuit switches off in the
heating mode.
H limit set temperature
If the average outside temperature is higher than the
set temperature, the heating circuit switches off in the
Set back mode.