Pellematic settings
80
Capacitive Sensor RA
Active
Activate the capacitive sensor on the burner.
0 = inactive
Capacitive Sensor ZW
Active
Activate the capacitive sensor on the hopper.
0 = inactive, 1 = active
Do you have a burner plate cleaning system, it runs parallel with the external de-
ashing system.
Note
Replace with: If the boiler has had no burner demand in 5 days the de-ashing
system will automatically activate on Friday at 12:00 for 3/5 minutes. This
prevents the settling of ash in the auger.
Before each ignition the de-ashing system and / or the burner plate cleaning system
are active for 20 seconds.
27.10 Boiler Controlled Pump
Boiler Controlled Pump
is in the Pellematic menu.
Boiler Controlled Pump has following menu items
• On Temp
• Depends On Require
• Speed Controller
• Switch Off Hyst
• Run On Time
• Control Range
Note
The output Boiler controlled Pump is limited
to 2.5A.
The additional menu items
Boiler Controlled Pump
are for the ÖkoFEN Service technician. They are present
after entering the code:
On Temp
When reaching the
On Temp
the output UW is activated or switched on the Boiler
Controlled Pump. The On Temp is the boiler temperature minimum.
Depends On Require
When reaching the
On Temp
and an existence of
Depends On Require
the output
UW is activated. (The burner run on time is considered)
Speed Controller
The
Speed Controller
allows (after their release - On Temp and Depends On
Require) the Boiler Controlled Pump in the cycling mode.
Switch Off Hyst
The
Switch Off Hyst
is the hysteresis for the boiler temperature minimum. It
prevents the clocking (ON OFF ON OFF) of the Boiler Controlled Pump.
Run On Time
The
Run on time
is how long the UW continues to run after the end of burner
demand. – in minutes
Control Range
Is the
Control Range
of output UW at cycling mode. The speed controller starts at
the boiler temperature minimum with a speed of 30% and increases to the boiler
temperature m
Control Range
up to 100% speed.
Operating manual Pelletronic Touch
E1389EN 2.0