Adesys bv, Wateringen, NL
Installation instructions
Octalarm-T2 / T4 / T8 / T16
45
KEYBOARD ACCESS: WITHOUT CODE / WITH CODE
Select whether the entire operation of the Octalarm has to be protected by an access code.
PROGRAMMING: WITHOUT CODE / WITH CODE
Select whether programming the Octalarm has to be protected by an access code. The
setting "with code" only protects the use of the cursor keys, the Prog-key and the esc-key.
The remaining keys can be operated in the usual way.
REMOTE SWITCHING.: WITHOUT CODE / WITH CODE
Select whether entering an access code, in order to switch a relay output by telephone, is
required.
REMOTE PROGRAM.: INHIBITED / WITH CODE
Select whether programming the Octalarm at a distance through the telephone line using a
PC and a modem is desired:
•
INHIBITED
programming at a distance is not possible.
•
WITH CODE
programming from distance is only possible after the access code is entered.
ACCESS CODE: 0000
Enter the 4-digit access code here.
Programming from a distance without the use of an access code is never possible.
18.11 Prog 71 “set night time mode”
Here you can define in what way the alarm report has to be carried out when the Octalarm functions in
night time mode.
AL. BUZZER NIGHT: OFF / ON
Define whether the use of the internal and external alarm buzzers is desirable in case of a
local alert at night. If so, the following options appear:
ALARM BUZZER ON: DIRECT AT ALARM / DIALLING FAILURE / AFTER DELAY
Set the start condition for the alarm buzzer:
DIRECT AT ALARM
the alarm buzzer sounds immediately after the detection of the alarm.
DIALLING FAILURE
the alarm buzzer only sounds after the complete failure of a telephone report
and also after 15 failing dialling attempts. The alarm buzzer will however sound immediately in
case the telephone dialler key is switched off.
AFTER DELAY
the alarm buzzer only sounds after the set delay time has elapsed. With this option,
the following additional question appears: