Adesys bv, Wateringen, NL
Installation instructions
Octalarm-T2 / T4 / T8 / T16
43
18.8 Prog 55 “set pager codes”
Setting an individual report code for each alarm channel and for all pager types is possible. The
following report codes are already pre-programmed:
channel
tone-only pagers
numerical pagers
alpha-numerical pagers and
SMS-messages
alarm 1
alarm 2
alarm 3
alarm 4
1
2
3
4
1
2
3
4
alarm 1
alarm 2
alarm 3
alarm 4
alarm 5
alarm 6
alarm 7
alarm 8
1
2
3
4
5
6
7
8
alarm 5
alarm 6
alarm 7
alarm 8
alarm 9
alarm 10
alarm 11
alarm 12
1
2
3
4
9
10
11
12
alarm 9
alarm 10
alarm 11
alarm 12
alarm 13
alarm 14
alarm 15
alarm 16
1
2
3
4
13
14
15
16
alarm 13
alarm 14
alarm 15
alarm 16
mains failure
4
9 or 90 (OT16)
mains failure
battery empty
4
10 or 91 (OT16)
battery empty / failure
18.8.1 Set report codes tone-only pager
Select the option:
SET REPORT CODES TONE-ONLY PAGER.
After the Prog-key is pressed, the following appears:
ALARM CHANNEL 1: 1
Here, enter the code (1 through 8) to appear on the pager in case alarm channel 1 is
activated.
When using the report codes 5 to 8, it must be checked if the pager can actually receive these
codes. Tone-only pagers are in fact supplied for 4 as well as for 8 report codes.
18.8.2 Set report codes numerical pager
Select the option:
SET REPORT CODES NUMERICAL PAGER.
After the Prog-key is pressed, the following appears:
ALARM CHANNEL 1: 1
Here, you enter the code to appear on the display of the numerical pager in case alarm
channel 1 is activated. The maximum number of digits to be set is 14.