18. INSTALLATION PROGRAMS
18.1 Prog 10 “set display contrast”
The contrast of the display can be adjusted using the
E
and
F
keys.
18.2 Prog 11 “ show version number”
After the Prog-key is pressed, the software version is shown on the display.
18.3 Prog 21 “set alarm inputs”
Select the output of which you want to modify or check the settings of. After confirming the selection
using the Prog-key, the following settings are available:
CONTACT INPUT 1: NORMALLY OPEN / NORMALLY CLOSED
Select whether the alarm has to be activated through a normally open contact or a normally closed
contact on the alarm input.
CONTACT INPUT 1: DIRECT / VIA SENSORNET
Select whether the alarm contact is directly connected to the Octalarm or whether it is connected by
means of a Sensornet terminal block (only for Octalarm -T4 and T8). See paragraph 16.3.1.2
“Connection through Sensornet”.
ALARM DELAY: 00:00 (MIN:SEC)
Set the desired alarm delay time. The alarm will only be issued after the activation of the alarm
exceeds this delay time.
MEMORY FUNCTION ON ALARM: OFF / ON
Define whether the report has to stop or whether it must be finished in case the alarm expires.
•
OFF
: both the local and telephone report are interrupted immediately in case the alarm expires.
•
ON
: the report will be completely finished in case the alarm expires. With this option, the following
additional question regarding the alarm indicator appears:
Reset memory: after teleph. Reset / by reset key
Define whether the alarm indicator has to extinguish by telephonic reset or whether it only can be
extinguished by pressing the reset key.
In case an alarm expires and re-occurs after having been reported, while the setting
on
is
activated, the report will start again, even if the alarm indicator on the Octalarm is still on. Also, the
use of this option will not result in reporting a recurring alarm only once.