Adesys bv, Wateringen, NL
Installation instructions
Octalarm-T2 / T4 / T8 / T16
47
18.13 Prog 97 “read data log”
The data log stores the most important alarm reports and/or program modifications in a permanent
memory. About 50 incidents with a time reference are stored together.
The data log uses a continuously working counter as a time reference. With each registration, the
corresponding counter reading is stored as well. If you subtract this time from the actual logging time,
you are able to find out exactly how long ago a certain incident took place. The time reference runs
until 1.000 hours at maximum, after which it is restarted at time 0 again. Reports older than 1.000
hours will be removed.
The following messages can occur in the data log:
General:
LOG TIME xxx: x
The actual log reference time in hours and minutes. When you read out the data log, this is
the first message to appear.
000:00 OCTALARM STARTED
The Octalarm had a complete restart. The time has been reset to 000:00 by this.
Program modifications:
XXX: XX CALL NR.. A: CHANGED
The call number (A) shown is changed on time xxx:xx.
XXX: XX PROG zz CHANGED
Program zz is changed on time xxx:xx. In case this regards Prog. 42 (dial sequence), the
alarm channel of which the order has been changed is indicated as well.
XXX: XX SELECTION: 1---567- T Z
At time xxx:xx, the position of the selection keys has been changed. In this example, the
alarm selection keys 1,5,6,7 and the telephone dialler and buzzer key are switched on, the
remaining selection keys are off. To prevent a message arising in the log with every key
touch (by which the log would quickly be full), the final position of the selection keys is only
stored 5 minutes after the last key touch.
Alarm reports:
XXX: XX MAINS FAILURE
XXX: XX BATTERY EMPTY
XXX: XX TEL. FAILURE
XXX: XX ALARM 1
At time xxx:xx, respectively a mains failure, a battery empty alarm, a telephone line
malfunctioning or an alarm 1 (external) has taken place. If the relevant selection key was
switched off at the time of an external alarm,
SEL. .KEY OFF
appears on the display as well.
In case the telephone dialler key was switched off at the time of an alarm, also
tel. dialler
off .
appears on the display. If the alarm channel is turned off in
מב
,
ALARM X OFF IN
DIALSEQ.
appears on the display.