Adesys bv, Wateringen, NL
Installation instructions
Octalarm-T2 / T4 / T8 / T16
37
18.4 Prog 23 “set alarm on display”
During an alarm, the Octalarm shows the number of the alarm channel and a user-definable message
on the display. The alarm cause can be reproduced in this way (for example "computer failure").
First select the input of which you want to modify or check the settings. After confirming the selection
using the Prog-key, the cursor appears on the lower line. Enter the alarm cause here. The maximum
text length is limited to 16 characters.
18.5 Prog 31 “set alarm buzzer”
This program allows you to set the start and stop conditions of the internal and external buzzer. The
following options are available:
ALARM BUZZER ON: DIRECT AT ALARM / DIALLING FAILURE / AFTER DELAY
Set the start condition for the alarm buzzer:
•
DIRECT AT ALARM
the alarm buzzer sounds immediately after the detection of the alarm.
•
DIALLING FAILURE
the alarm buzzer will only sound after the complete failure of a
telephone report, also following 15 failing dialling attempts. The alarm buzzer will however
sound immediately in case the telephone dialler key is switched off.
•
AFTER DELAY
the alarm buzzer only sounds after the set delay time has elapsed. With
this option, the following additional question appears:
DELAY TIME 01 MIN.
Set the desired delay time here (from 1 to 99 min).
ALARM BUZZER OFF: AFTER TEL. RESET / BY RESET KEY / AFTER DELAY
Set the stop condition for the alarm buzzer:
•
AFTER TEL. RESET
the alarm buzzer is switched off after a successful telephone report. The
buzzer keeps sounding after 15 failed report attempts. If the telephone dialler key is
switched off, the alarm buzzer will sound until the reset key is pressed.
•
BY RESET KEY
the alarm buzzer only stops after pressing the reset key.
•
AFTER DELAY
the alarm buzzer stops automatically after the set delay time has elapsed.
With this option, the following additional question appears:
DELAY TIME: 01 MIN.
Set the desired delay time here (from 1 to 99 min).
VOLUME INTERNAL BUZZER: 1/2/3
Select the desired volume for the built-in buzzer. The Octalarm enables you to hear the
chosen volume during adjustment. (The volume of the external buzzer can be adjusted to
three levels using the supplied reducer).