The wiring of the battery cell voltage and temperature sensing should be verified
before
connecting to the Cell Interface modules. The temperature sensing must be
isolated from the cell voltage sensing. Although the Cell Interface includes protective
circuitry to make it more resilient to brief wiring errors, the same circuitry can result
in the battery cells being slowly discharged. Over time, these wiring errors can cause
damage to the Cell Interface and/or the cells.
Table 15. Battery Cells: Molex Micro-Fit 3.0 Connector
Molex 43025-1800
Manufacturer
Molex Incorporated
Housing
43025-1800
Housing material
Nylon UL94V-0
Circuits
18
Crimp terminal
43030-0002
Wire gauge range
AWG20-24 stranded
Battery Cell Connector for Cell Interface - 12 channel
Table 16. Cell Interface - 12 channel Battery Cell Connector Pin Assignment
Pin
Connection
Description
Connected to Device
1
CELL0
Bottom reference of Cell Interface
Connect to negative terminal of
the lowest cell (Cell 1)
2
CELL2
Cell 2 voltage sense
Connect to positive terminal of
Cell 2
3
CELL4
Cell 4 voltage sense
Connect to positive terminal of
Cell 4
4
CELL6
Cell 6 voltage sense
Connect to positive terminal of
Cell 6
5
CELL8
Cell 8 voltage sense
Connect to positive terminal of
Cell 8
6
CELL10
Cell 10 voltage sense
Connect to positive terminal of
Cell 10
7
CELL12
Cell 12 voltage sense
Connect to positive terminal of
Cell 12
8
No Connect
Not Connected
No Connect
9
No Connect
Not Connected
No Connect
Nuvation Energy Stack Switchgear - Product Manual
Document ID: NE-PM-003
35
Rev 1.0, 2020-09-03