6.6. Calibrate the Nuvation Energy BMS
6.6.1. Overview
Before you start regular operation of your Nuvation Energy BMS, it is recommended that you calibrate
it for accurate usable capacity measurements.
This calibration should be done if changes are made to the energy storage installation or if a new
configuration file has been imported.
6.6.2. Calibration
1. Refer to the section
Measurement Calibration
in the
Software Reference Manual
for steps to
calibrate the stack current, voltage, and temperature measurements
2. Fully charge up the batteries to 100% State-of-Charge (as defined in the configuration file)
3. Discharge the batteries to 0% State-of-Charge (as defined in the configuration file)
4. Optionally, charge the batteries back up to 100% State-of-Charge
Nuvation Energy Stack Switchgear - Product Manual
Document ID: NE-PM-003
59
Rev 1.0, 2020-09-03