Figure 26. Example wiring 3 cells in a Cell Interface - 12V 4 channel
Temperature Sensors
The Temperature Sensors connector provides NTC thermistor inputs for temperature measurement of
the cells and/or surrounding area. All signals are referenced to Pin 1 of the
Battery Cells
connector.
The thermistors must be isolated from the cell voltage terminals in such a way that they will not
make an electrical connection to a cell terminal in the event of vibration/failures.
Connect 10 k
Ω
NTC thermistors to this connector.
Table 19. Temperature Sensors: Molex Micro-Fit 3.0 Connector
Molex 43025-1600
Manufacturer
Molex Incorporated
Housing
43025-1600
Housing material
Nylon UL94V-0
Circuits
16
Crimp terminal
43030-0002
Wire gauge range
AWG20-24 stranded
Nuvation Energy Stack Switchgear - Product Manual
Document ID: NE-PM-003
43