19
2. Air blow control during driving
When connecting the solenoid valve for DC24V to between
24V-P0, the solenoid valve can be turned on during driving the
load (being linked with driving). Please use it when you want to
turn ON/OFF the air for tooling auxiliary in time along with parts
feeder's driving.
The solenoid valve that can be connected is for DC24V. Use the
one with the surge killer of 0.5W or less.
<Internal circuit of valve driving>
The transistor is turned on when conditions
are satisfied, and the terminals P0 and 0V are
in continuity.
Switching capacity: DC30V, up to 0.1A
Note
The length of the cable connected to the output lines of 24V,
P0 and 0V, etc. should be within 10m. Please wire the device to
which a noise suppression element is attached.
Color of lead wire of the left figure is for reference. Please
check the actual color of lead wire in the instruction manual of
parts used, and connect.