10 Maintenance
PCS-9785 Satellite-Synchronized Clock
10-1
Date: 2019-07-05
This device is designed to require no special maintenance. All measurement and signal
processing circuit are fully solid state. All input modules are also fully solid state. The output relays
are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
10.1 Appearance Check
The device case should be clean without any dust stratification. Case cover should be sealed
well. No component has any mechanical damage and distortion, and they should be firmly
fixed in the case. Device terminals should be in good condition. The keys on the front panel
with very good feeling can be operated flexibly.
It is only allowed to plug or withdraw device board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the
primary system is live when withdrawing an AC module. Never try to insert or withdraw the
device board when it is unnecessary.
Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
10.2 Failure Tracing and Repair
Failures will be detected by automatic supervision or regular testing.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “
Superv State
” screen on the LCD.
When a failure is detected during regular testing, confirm the following:
Test circuit connections are correct
Modules are securely inserted in position
Correct DC power voltage is applied
Correct AC inputs are applied
Test procedures comply with those stated in the manual