8 Installation
PCS-9785 Satellite-Synchronized Clock
8-5
Date: 2019-07-05
effectively grounded to the frame by three braided copper strips (see
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTICE!
For metallic connection, please observe the voltage difference of both materials
according to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a
grounding strip (braided copper).
Figure 8.7-1 Cubicle grounding system
8.7.3 Device Ground Connection
There is a ground terminal on the rear panel, and the ground braided copper strip can be
connected with it. Take care that the grounding strip is always as short as possible. The main thing
is that the device is only grounded at one point. Grounding loops from unit to unit are not allowed.
There are some ground terminals on some connectors of this device, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this device. Therefore, the ground terminal on the
rear panel (see
) is the only ground terminal of this device.