4 Supervision
PCS-9785 Satellite Synchronized-Clock
4-2
Date: 2019-07-05
No.
Item
Description
14 Alm_Parity_IRIG-B2
Error is found during the parity check of IRIG-B2
15 Alm_Recv_IRIG-B1
The reception of IRIG-B1 is invalid
16 Alm_Recv_IRIG-B2
The reception of IRIG-B2 is invalid
17 Alm_Send_IRIG-B
The sending of IRIG-B signal is invalid.
The CLK module is failed.
18 PTP1.Alm_Conflict_ID_Clk An identical clock exists on the Precision Time Protocol (PTP) network1.
19 PTP2.Alm_Conflict_ID_Clk An identical clock exists on the Precision Time Protocol (PTP) network2
Table 4.1-2 Troubleshooting
No.
Item
Suggestion
1
Fail_Device
Inform the service agency for repair.
2
Alm_Initialization
Check external time source if the initialization failure has lasted for a long
period.
3
Alm_Device
Eliminate all the other alarms firstly.
4
Alm_DualDev
Verify the setting "Opt_DualDev" along with the device hardware.
5
Alm_Pwr1_Device
Check the rated input voltage and the PWR module 1.
6
Alm_Pwr2_Device
Check the rated input voltage and the PWR module 2.
7
Alm_Receiver_SatlCh1
Inform the service agency for repair.
8
Alm_Receiver_SatlCh2
Inform the service agency for repair.
9
Alm_SynLoss_SatlCh1
Check the wiring between the antenna 1 and the CLK module.
10 Alm_SynLoss_SatlCh2
Check the wiring between the antenna 2 and the CLK module.
11 Alm_Ant_SatlCh1
Check the antenna 1 installation and its connection with the CLK module.
12 Alm_Ant_SatlCh2
Check the antenna 2 installation and its connection with the CLK module.
13 Alm_Parity_IRIG-B1
Unify the parity check mode of both TX & RX for the IRIG-B1 link.
14 Alm_Parity_IRIG-B2
Unify the parity check mode of both TX & RX for the IRIG-B2 link.
15 Alm_Recv_IRIG-B1
Check the optical fiber connection for the IRIG-B1 reception link.
16 Alm_Recv_IRIG-B2
Check the optical fiber connection for the IRIG-B2 reception link.
17 Alm_Send_IRIG-B
Check the optical fiber connection for the IRIG-B sending link.
Check the CLK module.
18 PTP1.Alm_Conflict_ID_Clk
Check the IDs of all the clocks who are on the same PTP network.
PTP1: the network connected to the second optical port from the bottom of the
MON module
PTP2: the network connected to the last optical port of the MON module
19 PTP2.Alm_Conflict_ID_Clk
08020
08020
08020
08020
08020
08020
08020
08020
08020