7 Human Machine Interface
PCS-9785 Satellite-Synchronized Clock
7-4
Date: 2019-07-05
P3: To connect the RS-232 serial port of the computer.
The definition of the 8-core cable in the above figure is introduced in the following table.
No.
Core color
Function
Device side
(Left)
Computer side
(Right)
1
Orange & white
TX+ of the Ethernet port
P1-1
P2-1
2
Orange
TX- of the Ethernet port
P1-2
P2-2
3
Green & white
RX+ of the Ethernet port
P1-3
P2-3
4
Blue
TXD of the RS-232 serial port
P1-4
P3-2
5
Brown & white
RXD of the RS-232 serial port
P1-5
P3-3
6
Green
RX- for the Ethernet port
P1-6
P2-6
7
Blue & white
The ground connection of the RS-232 port.
P1-7
P3-5
8
Brown
P1-8
7.1.5 Ethernet Port Setup
MON plug-in module is equipped with two or four 100Base-TX Ethernet interface. Take
NR4106MB as an example, its rear view and the definition of terminals are shown in the following
figure.
The Ethernet port can be used to communication with PC via auxiliary software (PCS-Explorer)
after connecting the device with PC, so as to fulfill on-line function (please refer to the instruction
manual of PCS-Explorer). At first, the connection between the device and PC must be established.
Through setting the IP address and subnet mask of corresponding Ethernet interface in the menu
"
Settings
->
Comm Settings -> IP
", it should be ensured that the device and PC are in the same
network segment. For example, setting the IP address and subnet mask of network A. (using
network A to connect with PC)
PC: IP address is set as "198.87.96.102", subnet mask is set as "255.255.255.0"
The IP address and subnet mask of device should be [IP_LAN1] = 198.87.96.
XXX
, [Mask_LAN1]
=255.255.255.0, [En_LAN1] =1. (
XXX
can be any value from 0 to 255 except 102)
7.2 Menu Tree
NOTICE!
According to different applications in different engineering requirements, the display of
menu in HMI may be different.
7.2.1 Main Menu
Press "▲" in the normal display and enter the main menu. Select different submenu by "▲" and
"▼". Enter the selected submenu by pressing "
ENT
" or "►". Press "◄" and return to the previous
menu. Press "
ESC
" back to main menu directly.
08020
08020
08020
08020
08020
08020
08020
08020
08020