6 Settings
PCS-9785 Satellite Synchronized-Clock
6-7
Date: 2019-07-05
Ethernet port 1
Setting
Value
Bit0
Ethernet port 2
Bit2
3
Connected to ring network
Bit1
Bit3
1
1
0
0
Ethernet port 1
Setting
Value
Bit0
Ethernet port 3
Bit2
5
Connected to ring network
Bit1
Bit3
1
0
1
0
Ethernet port 1
Setting
Value
Bit0
Ethernet port 4
Bit2
9
Connected to ring network
Bit1
Bit3
1
0
0
1
Ethernet port 2
Setting
Value
Bit0
Ethernet port 3
Bit2
6
Connected to ring network
Bit1
Bit3
0
1
1
0
Ethernet port 2
Setting
Value
Bit0
Ethernet port 4
Bit2
10
Connected to ring network
Bit1
Bit3
0
1
0
1
Ethernet port 3
Setting
Value
Bit0
Ethernet port 4
Bit2
12
Connected to ring network
Bit1
Bit3
0
0
1
1
Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3
Cfg_NetPorts_Bond
Use this setting to set the channel bonding arrangement of two Ethernet ports in station level
communication.
For redundancy or increased throughput of the communication, dual network structure may
be adopted along with channel bonding technology. These two bonded interfaces, who share
the identical IP address and MAC address, work in Active-Standby mode. If the link via active
interface fails, the link via original standby interface will be activated automatically to ensure a
reliable communication.
The value of this setting represents a 4-bits binary number. Each bit represents a
corresponding Ethernet port's bonding status. Use the following map to decide the specific
setting value. Additionally, the default value "0" means the channel bonding function is
deactivated.