background image

8

 ~

 

ЕТ-485    

 

                                                                                                                                                                 

NOVATEK-ELECTRO

 

In  the  remote  server  redirection  mode,  if  connection  to  the  client-specified  Modbus  TCP  server  in  Ethernet 

network has been established, queries to other devices are also sent to this server and an answer from it is

 

awaited. 

N o te  

– The answer is received from the first answering addressee, therefore there must be no devices 

with same Modbus addresses (identifiers) in Modbus network and among the addressees, available through 
the remote server. 

If a query failed to be redirected (e.g. in the RS-485 slave mode, if connection to the remote server was broken), 

ET-485 can generate and transfer the client-specified Modbus exception code (default 

– code 10) to the client. 

If there is no answer, ET-485 can generate and transfer the client-specified Modbus exception code (default 

– 

code 11) to the client. 

If the answer to the query has been received, 

ЕТ-485 transfers it to the client, which sent the query. 

In  case  of  any  format  errors,  an  “Error”  indicator  shall  become  activated  for  0.5  seconds  and  no  response  is 
provided to the client.  

 

6.4 THE OPERATION OF ET-485 IN THE MODE OF ACTIVE CONNECTION TO THE CLIENT  
In this mode in addition to providing other connections

 

ET-485 autonomously establishes and further maintains 

active connection to the client (data collection remote server) with a set host name or IP address.  

ET-485 receives Modbus TCP queries from this client and returns responses. The mode allows one user to work with 

one or more ET-485 units via the Internet without static address assignment to each unit (see appendix B). 

 

 

7 SETTING 

7.1  GE N E R A L IN F ORMA T ION  
Configurable parameters are described in section 7.2. All parameters are saved at the power off. 
Unit configuration can be done in two ways:  

through WEB-interface, see Section 7.3; 

through Modbus-interface, see Section 7.4; 

 

WARNING!  ANY  CHANGES  IN  UNIT  CONFIGURATION  MAY  RESULT  IN  BLOCKING  OR 
OBSTRUCTION WHILE TRYING TO REACH THE UNIT OVER THE NETWORK. 
In this case, all parameters should be factory reset (see Section 3.2). 

 

7.2 P A R A ME T E R S  OF  

ЕТ-485 

A  collection  of  parameters  available  via  Modbus  protocol  is  provided  in  Table  3.  The  inner  structure  of  any 

collection of parameters is similar to the structure of collection, which is described in table 7 (apart from start-address). 

The presentation format of parameters in Modbus registers is detailed in Table 4. 
The unit describing parameters are given in Table 5. 
The unit current mode parameters are available for reading and recording and specified in Table 6. 
All parameters to determine the current condition of the unit (available for read-only) are provided in Table 7. 
All parameters available in the configuration mode only are provided in Table 8. 
ACC identification state parameters (table 9) are available for ACC and in a parameter mode. 
ACC identification control parameters are available only for ACC and are described in table 10. 

 

Table 3

 

– Collection of parameters available via Modbus protocol 

 

 

Collection 

Description 

Access 

Address 

Acting settings  Current unit configuration 

In any mode,  
read-only 

200

–298, 

1200

–1241 

Saved settings  The collection is saved regardless of power supply 

and further used as the restart. 

In configuration mode only, 
read-only 

300

–398, 

1300

–1341 

Factory 
settings 

Fixed collection, which can be activated as shown in 
sections 7.3 and 7.4 

In configuration mode only, 
read-only 

400

–498, 

1400

–1441 

Changeable 
settings 

All parameters listed in table 8, which can be modi-fied 
and incorporated as described in Section 7.4 

In configuration mode only, 
reading and writing 

500

–598, 

1500

–1541 

 
Table 4

 

– Presentation format of parameters in Modbus registers 

 

Parameter 

Range of values 

Description 

Number of 

Registers 

Number  0-65535 

Integer (16 bits) in a standard range of Modbus 
register 

 

Number 

0-4294967295 in two 
registers, 
 upper part 

– first 

Integer number, which can not exceed the limit for 
Modbus register (65535) 

 

Summary of Contents for ET-485

Page 1: ...perating conditions and wait at least 2 hours before connecting it to the electricity mains Do not use abrasives or organic compounds alcohol gasoline solvents etc for cleaning DO NOT OPEN AND REPAIR...

Page 2: ...6 6 2 Operating 485 over the HTTP protocol 7 6 3 Operating 485 over the Modbus TCP protocol 7 6 4 The operation of ET 485 in the mode of active connection to the client 8 7 SETTINGS 8 7 1 General info...

Page 3: ...onnecting side acts as a server Twisted pair is a pair of insulated conductors inside the cable which are twisted together in order to reduce the distortion of the transmitted signal Indicator is a LE...

Page 4: ...nit to the mains sec no more than 1 Utilized current in case of 220 V mA at most 10 Weight kg at most 0 200 Dimensions mm 95 52 67 Unit purpose Communication equipment Nominal operation condition cont...

Page 5: ...g while data exchange over the Ethernet network Figure 2 Front panel of ET 485 3 2 FUNCTIONING Simplified structural diagram of the unit is provided in Figure 3 32 digit RISC processor with ARM archit...

Page 6: ...CEDURE FOR 485 Suggested maintenance interval every six month The maintenance procedure includes visual inspection to verify the connection of cables to the 485 terminals as well as the absence of fra...

Page 7: ...ddress if connection filtering over IP is activated If this address does not correspond with the preset value the connection is rejected Otherwise the unit starts checking the list of available connec...

Page 8: ...NFIGURATION MAY RESULT IN BLOCKING OR OBSTRUCTION WHILE TRYING TO REACH THE UNIT OVER THE NETWORK In this case all parameters should be factory reset see Section 3 2 7 2 PARAMETERS OF 485 A collection...

Page 9: ...s Mode more detailed see register 141 0 User mode 1 Configuration mode 121 Current IP address IP address of the unit in Ethernet network 122 125 Current MAC address MAC address to authenticate the uni...

Page 10: ...1 the connected client has the permit for setting ET 485 similar to register 121 Bit 8 0 the client is not the main client 1 the client is the main client Bit 9 1 the client has the right for connecti...

Page 11: ...ed 1 setting parameters via Modbus interface or WEB interface is only allowed from the IP address of the main client 526 Enable the IP connections filter over Modbus TCP 0 1 0 0 Modbus TCP connections...

Page 12: ...sponse has not been received within the given time as indicated for the reception of res ponse Waiting time shall not be less then time required for transmission of a single character depending on the...

Page 13: ...additional client having IP address 127 0 0 1 587 Enable the Modbus TCP remote server query redirection mode 0 1 0 0 queries are not sent to remote server 1 queries are additionally sent to Modbus TC...

Page 14: ...ent 0 automatic sending is not accomplished 1 after active connection to the client the unit once sends 1000 1010 registers contents in the form of Modbus response without client query response 1000 1...

Page 15: ...ress IP address DHCP settings are modified and saved the browser may not load the page after the restart of the unit by pressing the Restart button This can happen as the browser continues to reply ov...

Page 16: ...se 9 5 The manufacturer s warranty does not apply to compensation for direct or indirect damages loss or injury associated with transporting the unit to the place of purchase or to the manufacturer 9...

Page 17: ...not necessary for communication between units in a subnet and is only used to connect units of one subnet to units of other networks Factory addressing settings for ET 485 Interface Converter are lis...

Page 18: ...roperties Figure 2 TCP IP properties window in Windows OS window in Windows OS 3 SWITCHING TO INTERNET WARNING The user is strongly recommended to connect the unit to Internet under the supervision of...

Page 19: ...ET 485 IP address filters for recording and or reading can be enabled to provide to a single client the permit to request via Modbus protocol such function codes which are not reading functions unit s...

Page 20: ...direction of queries If the unit whereto the queries are redirected is set to such redirection that the query will be transferred to its initial sender the queries will be transferred nonstop which wi...

Page 21: ...w unit can be specified as the main client It allows increasing the number of RS 485 connected devices and simultaneously connected Modbus TCP clients by 10 for every additional ET 485 unit Each of th...

Page 22: ...g receiving alert messages about incidents via SMS or E Mail Overvis system maintains ACC mode used in ET 485 acting as a data collection server of many simultaneously connected units and providing ac...

Page 23: ...etc b client uses unique MAC address of the unit for its identification In order to provide the access for the user the unique activation code is given to each unit herewith Modbus write protection m...

Page 24: ...ode Symbol 32 64 96 33 65 A 97 A 34 66 B 98 B 35 67 C 99 C 36 68 D 100 D 37 69 E 101 E 38 70 F 102 f 39 71 G 103 g 40 72 H 104 h 41 73 I 105 i 42 74 J 106 j 43 75 K 107 k 44 76 L 108 l 45 77 M 109 m 4...

Page 25: ...AC110 61F GPN V50 AC110 70177 1011 F03 03 HAS B F03 03 HAS C F03 31 81513201 81513535 81550401 FT1A C12RA W 88981106 H2CAC24A R88A CAGA005S R88A CRGB003CR E R88ARR080100S R88A TK01K DCN1 1 DTB4896VRE...

Reviews: