12
~
ЕТ-485
NOVATEK-ELECTRO
Parameter
Min
–
Max
Factory
setting
Description
Address
Enable the odd-
even check
0
–1
0
Used in case of data exchange between the units in
Modbus-network, the same value for all units in Modbus-
network
0: unused, byte is completed with 2 stop bits
1: byte is completed with parity bit and 1 stop bit
536
Enable the odd-
even check
(to verify odds)
0
–1
0
Used in case of data exchange between the units in
Modbus-network, if odd-even check is enabled. The same
value for all units in Modbus-network
0: Parity check
1: Imparity check
537
Response time
from Modbus
RTU, msec
0
–60 000
200
Used in case of data transfer via the Modbus-network in
RTU mode. Waiting for a response is terminated if the first
byte of the response has not been received within the
given time after sending the request. The response is
always expected longer then time of silence between
frames (time of silence depends on the bit rate and shall
be equal to the time required for transmitting 3.5 bytes, or
1.75 msec for bit rate over 19,200 bits/sec).
538
Enable ASCII
exchange in
Modbus network
0
–1
0
Exchange mode in Modbus-network, the same value for
all units in Modbus-network
0: RTU exchange mode (format: 1start bit, 8 data bits, 1
parity bit or stop-bit or 1 stop bit
– total 11 bits).
1: ASCII exchange mode (format: 1start bit, 7 data bits, 1
parity bit or stop-bit or 1 stop bit
– total 10 bits).
539
Response time
for subsequent
Modbus ASCII
character, msec
0
–60 000
1000
Used in case of data transfer via the Modbus-network in
ASCII mode. Waiting for a response is terminated if the
subsequent byte of the response has not been received
within the given time, as indicated for the reception of res-
ponse. Waiting time shall not be less then time required for
transmission of a single character (depending on the bit rate).
540
Miscellaneous
Enable the unit
automatic reset
0
–1
0
0: periodical reset is off
1: the unit is reset after a preset time interval
541
Unit restart
interval, min
5
–7200
7200
Used if periodic restart of the unit is enabled
542
Password to
enter the setup
mode
String of
charac-
ters
11111
Used to access the setup mode for Modbus TCP. Any
string of 5 to 20 characters can be used as a password. It
may not contain spaces or special characters listed in
quotes below:
«; : " < > * + = \ | / ? ,»
543
–
562
The preset
password for
permit to record
to devices,
connected to
ET-485
Symbol
string
Used for access to the devices, connected to ET-485, for
requesting functions of recording or control, which can
change the state of these devices. As a password one
may specify a string with length up to 6 symbols. The
string must not contain any spaces or special symbols,
given below in quotes:
“; : " < > * + = \ | / ? ,”
563
–568
The preset
password for
permit to read
from devices,
connected to
ET-485
Symbol
string
Used for access to the devices, connected to ET-485, for
requesting functions of reading, which do not affect the
state of these devices. As a password one may specify a
string with length up to 6 symbols. The string must not
contain any spaces or special symbols, given below in
quotes:
“; : " < > * + = \ | / ? ,”
569
–574
The preset pas-
sword for access
to ET-485
registers of state
and settings
Symbol
string
Used for access to ET-485 registers, except for the
registers of version, password, mode and flags. As a
password one may specify a string with length up to 6
symbols. The string must not contain any spaces or
special symbols, given below in quotes:
“; : " < > * + = \ | / ? ,”
575
–580