background image

18

 ~

 

ЕТ-485    

 

                                                                                                                                                                 

NOVATEK-ELECTRO

 

Next, perform the following steps: 

1) 

In the Connections window, select the desired connection via an adapter with the addressing that you want 
to  change.  Many  computers  have  only  one  adapter  and  one  connection,  which  will  be  displayed  in  this 
window. If the window shows several connections, select the connection you want , using the adapter name 
in the information on connection or contact your system administrator. 

2) 

Click  the icon  of  the  connection  with  the  right  button,  and  select  "Properties"  in  the  drop-down menu. The 
Properties window opens (see Fig. A.1).  

3) 

Select  "Internet  Protocol  (TCP/IP)"  from  the  list  of connection  components  in  the  next  window.  Make  sure 
that the component is enabled (flagged in the list) . Click "Properties". The TCP/IP properties window opens 
(see Fig. A.2). 

4) 

Select "Use the following IP- address". 

5) 

Specify the address in the "IP- address" field within the range from 192.168.0.1 to 192.168.0.255 (except for 
192.168.0.111, which is used by ET-485). 

6) 

Specify "255.255.255.0" in the “Subnet Mask” field. 

7) 

The fields "Default Gateway", "Preferred DNS-server", and "Alternative DNS- server" should be left blank. 

8) 

Press "OK" to close the Protocol Settings window. 

9) 

Press "OK" to close the Connections Settings window. 

10) 

If prompted by the OS to restart the PC after closing the windows, answer yes.  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

            Figure 

А.1

 

– Connection properties                                        

Figure 

А.2

 

– TCP/IP properties  

                                 window in Windows OS                                                             window in Windows OS 

 
 

3. SWITCHING TO INTERNET 

 

WARNING!  The  user  is  strongly  recommended  to  connect  the  unit  to  Internet  under  the 
supervision of the LAN system administrator and/or representative of Internet service provider

.

 

                

Use the following guidelines to connect the unit to Internet: 

acquire a dedicated line with a static IP-address from your Internet Service Provider (hereinafter referred to as 

– 

ISP; for connection with dynamic IP address it is necessary to use active connection to the client, see annex B);  

several  connection  options  are  possible  if  your  ISP  binds  the  connection  to  MAC-address,  and  the  given 

Internet connection was already used by personal computers or other units:

 

 a) connect the unit directly to the PC (see Section 5.2.1) to learn the MAC-address of the unit (see Section 7). 

Inform the ISP on the change of MAC-address to the MAC-address of the unit; 

 b) determine the MAC-address for Internet connection from the unit settings, which was previously using this 

connection,  or  acquire  it  from  your  ISP.  Connect  the  unit  directly  to  the  PC  and  change  the  parameters  "Enable 
manual MAC-address" and "Manually set MAC-address" to have the manual MAC-address enabled and values of 
the unit correspond to MAC- address with an Internet connection binded; 

direct  connection  of  the  unit  to  the  ISP  cable  is  not  recommended;  in  case  of  a  router  connection,  the  ISP 

cable  is  connected  to  the  "Uplink"  socket  on  the  router  (It  is  usually marked with  color  and  has no  numbers.  The 

Summary of Contents for ET-485

Page 1: ...perating conditions and wait at least 2 hours before connecting it to the electricity mains Do not use abrasives or organic compounds alcohol gasoline solvents etc for cleaning DO NOT OPEN AND REPAIR...

Page 2: ...6 6 2 Operating 485 over the HTTP protocol 7 6 3 Operating 485 over the Modbus TCP protocol 7 6 4 The operation of ET 485 in the mode of active connection to the client 8 7 SETTINGS 8 7 1 General info...

Page 3: ...onnecting side acts as a server Twisted pair is a pair of insulated conductors inside the cable which are twisted together in order to reduce the distortion of the transmitted signal Indicator is a LE...

Page 4: ...nit to the mains sec no more than 1 Utilized current in case of 220 V mA at most 10 Weight kg at most 0 200 Dimensions mm 95 52 67 Unit purpose Communication equipment Nominal operation condition cont...

Page 5: ...g while data exchange over the Ethernet network Figure 2 Front panel of ET 485 3 2 FUNCTIONING Simplified structural diagram of the unit is provided in Figure 3 32 digit RISC processor with ARM archit...

Page 6: ...CEDURE FOR 485 Suggested maintenance interval every six month The maintenance procedure includes visual inspection to verify the connection of cables to the 485 terminals as well as the absence of fra...

Page 7: ...ddress if connection filtering over IP is activated If this address does not correspond with the preset value the connection is rejected Otherwise the unit starts checking the list of available connec...

Page 8: ...NFIGURATION MAY RESULT IN BLOCKING OR OBSTRUCTION WHILE TRYING TO REACH THE UNIT OVER THE NETWORK In this case all parameters should be factory reset see Section 3 2 7 2 PARAMETERS OF 485 A collection...

Page 9: ...s Mode more detailed see register 141 0 User mode 1 Configuration mode 121 Current IP address IP address of the unit in Ethernet network 122 125 Current MAC address MAC address to authenticate the uni...

Page 10: ...1 the connected client has the permit for setting ET 485 similar to register 121 Bit 8 0 the client is not the main client 1 the client is the main client Bit 9 1 the client has the right for connecti...

Page 11: ...ed 1 setting parameters via Modbus interface or WEB interface is only allowed from the IP address of the main client 526 Enable the IP connections filter over Modbus TCP 0 1 0 0 Modbus TCP connections...

Page 12: ...sponse has not been received within the given time as indicated for the reception of res ponse Waiting time shall not be less then time required for transmission of a single character depending on the...

Page 13: ...additional client having IP address 127 0 0 1 587 Enable the Modbus TCP remote server query redirection mode 0 1 0 0 queries are not sent to remote server 1 queries are additionally sent to Modbus TC...

Page 14: ...ent 0 automatic sending is not accomplished 1 after active connection to the client the unit once sends 1000 1010 registers contents in the form of Modbus response without client query response 1000 1...

Page 15: ...ress IP address DHCP settings are modified and saved the browser may not load the page after the restart of the unit by pressing the Restart button This can happen as the browser continues to reply ov...

Page 16: ...se 9 5 The manufacturer s warranty does not apply to compensation for direct or indirect damages loss or injury associated with transporting the unit to the place of purchase or to the manufacturer 9...

Page 17: ...not necessary for communication between units in a subnet and is only used to connect units of one subnet to units of other networks Factory addressing settings for ET 485 Interface Converter are lis...

Page 18: ...roperties Figure 2 TCP IP properties window in Windows OS window in Windows OS 3 SWITCHING TO INTERNET WARNING The user is strongly recommended to connect the unit to Internet under the supervision of...

Page 19: ...ET 485 IP address filters for recording and or reading can be enabled to provide to a single client the permit to request via Modbus protocol such function codes which are not reading functions unit s...

Page 20: ...direction of queries If the unit whereto the queries are redirected is set to such redirection that the query will be transferred to its initial sender the queries will be transferred nonstop which wi...

Page 21: ...w unit can be specified as the main client It allows increasing the number of RS 485 connected devices and simultaneously connected Modbus TCP clients by 10 for every additional ET 485 unit Each of th...

Page 22: ...g receiving alert messages about incidents via SMS or E Mail Overvis system maintains ACC mode used in ET 485 acting as a data collection server of many simultaneously connected units and providing ac...

Page 23: ...etc b client uses unique MAC address of the unit for its identification In order to provide the access for the user the unique activation code is given to each unit herewith Modbus write protection m...

Page 24: ...ode Symbol 32 64 96 33 65 A 97 A 34 66 B 98 B 35 67 C 99 C 36 68 D 100 D 37 69 E 101 E 38 70 F 102 f 39 71 G 103 g 40 72 H 104 h 41 73 I 105 i 42 74 J 106 j 43 75 K 107 k 44 76 L 108 l 45 77 M 109 m 4...

Page 25: ...AC110 61F GPN V50 AC110 70177 1011 F03 03 HAS B F03 03 HAS C F03 31 81513201 81513535 81550401 FT1A C12RA W 88981106 H2CAC24A R88A CAGA005S R88A CRGB003CR E R88ARR080100S R88A TK01K DCN1 1 DTB4896VRE...

Reviews: