background image

20

 ~

 

ЕТ-485    

 

                                                                                                                                                                 

NOVATEK-ELECTRO

 

 

APPENDIX B 

(recommended) 

EXAMPLES OF NETWORKS TOPOLOGY 

 

1. ACCESS TO RS-485 NETWORK FROM ETHERNET NETWORK 

 

 

 

Figure B.1

 

– Access to RS-485 network (Modbus RTU/ASCII) via Ethernet (Modbus TCP) network 

 

ET-485 is used in the RS-485 master mode, receiving queries from clients in Ethernet or Internet network. The 

queries are sent to Modbus network. Redirection to remote server is not used. 

 

2. MODBUS NETWORK EXTENSION 

 

Two ET-485 units are used, connected as shown in Figure B.2. 
ET-485 

“a” is connected in the slave mode to RS-485 Modbus “A” network (with a master device). ET-485 “b” is 

connected  in  the  master  mode  with  a  static  IP  address  to  Modbus 

“B” network (with slave devices). Both units are 

connected into one 

Ethernet network or connected by means of routers via Internet so that unit “a” can be connected 

to unit “b”. 

Unit “a” is set for query redirection to the remote server with Modbus TCP address and port, which unit “b” has. 

All Modbus devices, including both ET-485 units and devices in both Modbus networks, must have different Modbus 
addresses (identifiers.) The queries, sent by the master device in 

“A” network, are redirected by unit “a” to unit “b”. 

Unit “b” sends them to the devices in “B” network. 

N o te  

– One should avoid cyclic redirection of queries. If the unit, whereto the queries are redirected, is 

set to such redirection that the query will be transferred to its initial sender, the queries will be transferred 
nonstop, which will cause slowdown and then shutdown of query processing by these units. 

 

If  some  other  devices,  besides  the  master  device  and  ET-485 

unit  “a”,  are  connected  in  “A”  network,  the 

exception code generation must be disabled in the settings of ET-485 units, if there is no answer and no connection. 
Otherwise,  while  the  master  device  is  sending  queries  to  other  slave  devices  in  “A”  network,  ET-485  unit  “a”  can 
generate or transfer an exception code, received from unit “b”, simultaneously with transferring a correct answer from 
another device, which will result in network collision. 

 

3. INCREASE OF THE NUMBER OF SIMULTANEOUSLY CONNECTED DEVICES 

 

The diagram in Figure B.2 allows connecting the number of devices, specified in the technical characteristics, 

giving the opportunity to double the number of devices, available to the master device.

  

 
4. MATCHING OF MODBUS NETWORKS 

 

The diagram in Figure B.2 also allows connecting two Modbus networks with different characteristics: Modbus 

RTU network and ASCII network, networks with different exchange rates etc. herewith, each ET-485 unit is set for 
the corresponding characteristics of its Modbus network, and sufficient delays for passing and processing of queries 
and answers are chosen for both units. 

Summary of Contents for ET-485

Page 1: ...perating conditions and wait at least 2 hours before connecting it to the electricity mains Do not use abrasives or organic compounds alcohol gasoline solvents etc for cleaning DO NOT OPEN AND REPAIR...

Page 2: ...6 6 2 Operating 485 over the HTTP protocol 7 6 3 Operating 485 over the Modbus TCP protocol 7 6 4 The operation of ET 485 in the mode of active connection to the client 8 7 SETTINGS 8 7 1 General info...

Page 3: ...onnecting side acts as a server Twisted pair is a pair of insulated conductors inside the cable which are twisted together in order to reduce the distortion of the transmitted signal Indicator is a LE...

Page 4: ...nit to the mains sec no more than 1 Utilized current in case of 220 V mA at most 10 Weight kg at most 0 200 Dimensions mm 95 52 67 Unit purpose Communication equipment Nominal operation condition cont...

Page 5: ...g while data exchange over the Ethernet network Figure 2 Front panel of ET 485 3 2 FUNCTIONING Simplified structural diagram of the unit is provided in Figure 3 32 digit RISC processor with ARM archit...

Page 6: ...CEDURE FOR 485 Suggested maintenance interval every six month The maintenance procedure includes visual inspection to verify the connection of cables to the 485 terminals as well as the absence of fra...

Page 7: ...ddress if connection filtering over IP is activated If this address does not correspond with the preset value the connection is rejected Otherwise the unit starts checking the list of available connec...

Page 8: ...NFIGURATION MAY RESULT IN BLOCKING OR OBSTRUCTION WHILE TRYING TO REACH THE UNIT OVER THE NETWORK In this case all parameters should be factory reset see Section 3 2 7 2 PARAMETERS OF 485 A collection...

Page 9: ...s Mode more detailed see register 141 0 User mode 1 Configuration mode 121 Current IP address IP address of the unit in Ethernet network 122 125 Current MAC address MAC address to authenticate the uni...

Page 10: ...1 the connected client has the permit for setting ET 485 similar to register 121 Bit 8 0 the client is not the main client 1 the client is the main client Bit 9 1 the client has the right for connecti...

Page 11: ...ed 1 setting parameters via Modbus interface or WEB interface is only allowed from the IP address of the main client 526 Enable the IP connections filter over Modbus TCP 0 1 0 0 Modbus TCP connections...

Page 12: ...sponse has not been received within the given time as indicated for the reception of res ponse Waiting time shall not be less then time required for transmission of a single character depending on the...

Page 13: ...additional client having IP address 127 0 0 1 587 Enable the Modbus TCP remote server query redirection mode 0 1 0 0 queries are not sent to remote server 1 queries are additionally sent to Modbus TC...

Page 14: ...ent 0 automatic sending is not accomplished 1 after active connection to the client the unit once sends 1000 1010 registers contents in the form of Modbus response without client query response 1000 1...

Page 15: ...ress IP address DHCP settings are modified and saved the browser may not load the page after the restart of the unit by pressing the Restart button This can happen as the browser continues to reply ov...

Page 16: ...se 9 5 The manufacturer s warranty does not apply to compensation for direct or indirect damages loss or injury associated with transporting the unit to the place of purchase or to the manufacturer 9...

Page 17: ...not necessary for communication between units in a subnet and is only used to connect units of one subnet to units of other networks Factory addressing settings for ET 485 Interface Converter are lis...

Page 18: ...roperties Figure 2 TCP IP properties window in Windows OS window in Windows OS 3 SWITCHING TO INTERNET WARNING The user is strongly recommended to connect the unit to Internet under the supervision of...

Page 19: ...ET 485 IP address filters for recording and or reading can be enabled to provide to a single client the permit to request via Modbus protocol such function codes which are not reading functions unit s...

Page 20: ...direction of queries If the unit whereto the queries are redirected is set to such redirection that the query will be transferred to its initial sender the queries will be transferred nonstop which wi...

Page 21: ...w unit can be specified as the main client It allows increasing the number of RS 485 connected devices and simultaneously connected Modbus TCP clients by 10 for every additional ET 485 unit Each of th...

Page 22: ...g receiving alert messages about incidents via SMS or E Mail Overvis system maintains ACC mode used in ET 485 acting as a data collection server of many simultaneously connected units and providing ac...

Page 23: ...etc b client uses unique MAC address of the unit for its identification In order to provide the access for the user the unique activation code is given to each unit herewith Modbus write protection m...

Page 24: ...ode Symbol 32 64 96 33 65 A 97 A 34 66 B 98 B 35 67 C 99 C 36 68 D 100 D 37 69 E 101 E 38 70 F 102 f 39 71 G 103 g 40 72 H 104 h 41 73 I 105 i 42 74 J 106 j 43 75 K 107 k 44 76 L 108 l 45 77 M 109 m 4...

Page 25: ...AC110 61F GPN V50 AC110 70177 1011 F03 03 HAS B F03 03 HAS C F03 31 81513201 81513535 81550401 FT1A C12RA W 88981106 H2CAC24A R88A CAGA005S R88A CRGB003CR E R88ARR080100S R88A TK01K DCN1 1 DTB4896VRE...

Reviews: