ЕТ-485    

 

                                                                                                                                                                 

NOVATEK-ELECTRO

 

Parameter 

 Min 

– 

Max 

Factory 

setting 

Description 

Address 

Modbus code of 
exception, gene-
rated at absence 
of answer from 
query addressee 

 
 

0

–255 

 
 

11 

0:  If  there  is  no  answer  from  the  query  addressee 
(Gateway  Timeout),  the  answer  is  not  returned  to  the 
client. 
1-255: If there is no answer from the query addressee, this 
exception code is returned to the client. 

 
 

598 

ACC settings

 

Enable using of 
DNS server with 
gateway IP 
address 

 

0

–1 

 

Used when DHCP is not available (is off) 
0: DNS of gateway is not used 
1: DNS of gateway is used to identify client (or DCRS) IP ad-
dress for active connection, if its address is set as host name 

 

1500 

Enable  using  of 

DNS  server  with 
manually  set  IP 
address 

 

0

–1 

 

Used when DHCP is not available (is off) 
0: DNS with manually set IP is not used 
1:  DNS  with  manually  set  IP  is  used  to  identify  client  (or 

DCRS)  IP  address  for  active  connection,  if  its  address  is 
set as host name 

 

1501 

Manually  set  IP 

address  of  DNS 
server 

IP 

address 

 

8.8.8.8 

Used  when  manual  address  of  DNS  server  is  enabled  in 

order  to  identify  client  (or  DCRS)  IP  address  for  active 
connection, if its address is set as host name 

 

1502

1505 

Enable 

active 

connection 

to 

the client  

 

0

–1 

 

0: active connection to the client is not used 
1:  Modbus  queries  are  also  received  from  the  client  (or 
DCRS) with set address, to which ET-485 establishes and 
maintains  connection.  This  client  recieves  rights  of  the 
second primary ET-485 client  

 

1506 

Enable  sending 
of  unique  MAC 
address  of  the 
unit  after  active 
connection 

to 

the client 

 

0

–1 

 

Used in the mode of active connection to the client. 
0: automatic sending is not accomplished 
1: after active connection to the client the unit once sends 
1000

–1010  registers  contents  in  the  form  of  Modbus 

response  without  client  query  (response 

–  1000–1010 

registers reading by function 3) 

 

1507 

Timeout 

until 

repeated  active 
connection 

to 

the client, sec 

 

0

30 000 

 
 

20 

Used  in  the  active  connection  to  the  client  mode.  After 
loss  of  active  connection  to  the  client,  repeated 
connection  will  be  established  after  present  connection 
timeout  (after  setting  of  the  unit  the  first  connection  is 
established after the fixed time interval of 5 seconds). 

 
 

1508 

Client port (or 
DCRS) for ac-
tive connection 

 

0

65535 

 

20502 

Used in the mode of active connection to the client. Client 
(or  DCRS)  port,  to  which  ET-485  establishes  active 
connection. 

 

1509 

Client (or

 

DCRS) 

address for ac-
tive connection 

Symbol 
string 

modbus. 

overvis.com 

Used  in  the  mode  of  active  connection  to  the  client.  IP 
address  (or  host  name)  of  the  client  or  DCRS  for  active 
connection 

1510

1541 

 
 

Table 9 

– State of unit identification for ACC 

 

Parameter 

Description 

Address 

Unit type 

see register 0 

1000 

Firmware version 

see register 1 

1001 

Unique MAC address 

Globally unique MAC address of the unit, which can be used for 
identification by the client 

1002

1007 

 

ACC state flags  

Bit 0 

0:  0: error of unique MAC address reading 

1:  registers  1002

–1007  contain  globally  unique  MAC 

address 

 

1008 

Bit 1 

0: 0: activation code on the data collection server is not set 

1: activation code on the data collection server is set 

Bit 2 

0:  ET-485  does  not  require  new  activation  code  from 
the data collection server  
1:  ET-485  requires  new  activation  code  from  the  data 
collection server 

Bit 3 

0:  connection  is  not  activated  by  the  data  collection 
server  

1:connection is activated by the data collection server 

Summary of Contents for ET-485

Page 1: ...perating conditions and wait at least 2 hours before connecting it to the electricity mains Do not use abrasives or organic compounds alcohol gasoline solvents etc for cleaning DO NOT OPEN AND REPAIR...

Page 2: ...6 6 2 Operating 485 over the HTTP protocol 7 6 3 Operating 485 over the Modbus TCP protocol 7 6 4 The operation of ET 485 in the mode of active connection to the client 8 7 SETTINGS 8 7 1 General info...

Page 3: ...onnecting side acts as a server Twisted pair is a pair of insulated conductors inside the cable which are twisted together in order to reduce the distortion of the transmitted signal Indicator is a LE...

Page 4: ...nit to the mains sec no more than 1 Utilized current in case of 220 V mA at most 10 Weight kg at most 0 200 Dimensions mm 95 52 67 Unit purpose Communication equipment Nominal operation condition cont...

Page 5: ...g while data exchange over the Ethernet network Figure 2 Front panel of ET 485 3 2 FUNCTIONING Simplified structural diagram of the unit is provided in Figure 3 32 digit RISC processor with ARM archit...

Page 6: ...CEDURE FOR 485 Suggested maintenance interval every six month The maintenance procedure includes visual inspection to verify the connection of cables to the 485 terminals as well as the absence of fra...

Page 7: ...ddress if connection filtering over IP is activated If this address does not correspond with the preset value the connection is rejected Otherwise the unit starts checking the list of available connec...

Page 8: ...NFIGURATION MAY RESULT IN BLOCKING OR OBSTRUCTION WHILE TRYING TO REACH THE UNIT OVER THE NETWORK In this case all parameters should be factory reset see Section 3 2 7 2 PARAMETERS OF 485 A collection...

Page 9: ...s Mode more detailed see register 141 0 User mode 1 Configuration mode 121 Current IP address IP address of the unit in Ethernet network 122 125 Current MAC address MAC address to authenticate the uni...

Page 10: ...1 the connected client has the permit for setting ET 485 similar to register 121 Bit 8 0 the client is not the main client 1 the client is the main client Bit 9 1 the client has the right for connecti...

Page 11: ...ed 1 setting parameters via Modbus interface or WEB interface is only allowed from the IP address of the main client 526 Enable the IP connections filter over Modbus TCP 0 1 0 0 Modbus TCP connections...

Page 12: ...sponse has not been received within the given time as indicated for the reception of res ponse Waiting time shall not be less then time required for transmission of a single character depending on the...

Page 13: ...additional client having IP address 127 0 0 1 587 Enable the Modbus TCP remote server query redirection mode 0 1 0 0 queries are not sent to remote server 1 queries are additionally sent to Modbus TC...

Page 14: ...ent 0 automatic sending is not accomplished 1 after active connection to the client the unit once sends 1000 1010 registers contents in the form of Modbus response without client query response 1000 1...

Page 15: ...ress IP address DHCP settings are modified and saved the browser may not load the page after the restart of the unit by pressing the Restart button This can happen as the browser continues to reply ov...

Page 16: ...se 9 5 The manufacturer s warranty does not apply to compensation for direct or indirect damages loss or injury associated with transporting the unit to the place of purchase or to the manufacturer 9...

Page 17: ...not necessary for communication between units in a subnet and is only used to connect units of one subnet to units of other networks Factory addressing settings for ET 485 Interface Converter are lis...

Page 18: ...roperties Figure 2 TCP IP properties window in Windows OS window in Windows OS 3 SWITCHING TO INTERNET WARNING The user is strongly recommended to connect the unit to Internet under the supervision of...

Page 19: ...ET 485 IP address filters for recording and or reading can be enabled to provide to a single client the permit to request via Modbus protocol such function codes which are not reading functions unit s...

Page 20: ...direction of queries If the unit whereto the queries are redirected is set to such redirection that the query will be transferred to its initial sender the queries will be transferred nonstop which wi...

Page 21: ...w unit can be specified as the main client It allows increasing the number of RS 485 connected devices and simultaneously connected Modbus TCP clients by 10 for every additional ET 485 unit Each of th...

Page 22: ...g receiving alert messages about incidents via SMS or E Mail Overvis system maintains ACC mode used in ET 485 acting as a data collection server of many simultaneously connected units and providing ac...

Page 23: ...etc b client uses unique MAC address of the unit for its identification In order to provide the access for the user the unique activation code is given to each unit herewith Modbus write protection m...

Page 24: ...ode Symbol 32 64 96 33 65 A 97 A 34 66 B 98 B 35 67 C 99 C 36 68 D 100 D 37 69 E 101 E 38 70 F 102 f 39 71 G 103 g 40 72 H 104 h 41 73 I 105 i 42 74 J 106 j 43 75 K 107 k 44 76 L 108 l 45 77 M 109 m 4...

Page 25: ...AC110 61F GPN V50 AC110 70177 1011 F03 03 HAS B F03 03 HAS C F03 31 81513201 81513535 81550401 FT1A C12RA W 88981106 H2CAC24A R88A CAGA005S R88A CRGB003CR E R88ARR080100S R88A TK01K DCN1 1 DTB4896VRE...

Reviews: