15

 ~

 

NOVATEK-ELECTRO

                                                                                                          ЕТ-485    

 

                                                                                                                                   

 

 
Table 10 

– Unit identification control for ACC  

 

Parameter 

Min.

–Max. 

Initial value 

Description  

Address 

 

Activation 

code on the 

data 

collection 

server 

 
 

10 000 000 

– 

100 000 000 

or 0 

 
 

100 000 000 

Code,  transferred  from  data  collection  server  and 

displayed  on  the  unit  setting  page  through  WEB 
interface (p. 7.3). When user enters the code on the 
data collection server, the unit and ACC connection 
become available to this user. 

– connection is activated 

10  000  000 

–  99 999 999:  activation  code 

100 000 000: code is not assigned 

 
 

1009

–1010 

7.3 CONFIGURING 

ЕТ-485 THROUGH WEB INTERFACE 

WEB-browser is used for setting via WEB-interface. 
Write the unit IP-address in your browser (factory setting - 192.168.0.111) and proceed to the specified address. 

 

Note  -  If  the  browser  is  set  to  use  the  proxy  server,  the  access  to  the  unit  over  local  network  shall  be 

granted only after adding the IP- address into the exceptions list as indicated in the browser documentation. 

 

This will open home page with tabs for transferring into the other modes. 
Select “Settings” to start the configuration of unit Ethernet network.  
Password request shall appear before granting access to setup mode (factory setting 11111). 
Enter password and press "Enter". If the password is correct, you shall be granted access to the setup mode. 

Settings  page  appears  with  a  list  of  parameters  detailed  in  Table  8.  If  the  password  is  incorrect,  the  password 
request shall be displayed once again. 

Click  "Save"  after making  changes  to  the  settings. This  will  check  all  the changed  parameters.  If no errors  is 

detected, new parameters will be stored in the memory (new parameters will become effective upon the following 
restart/activation of the unit). In case of any errors detected upon clicking the "Save" button, none of the parameters 
is saved, while the names of erroneous parameters are highlighted in red. 

Click "Factory reset" to restore the default value of parameters. 
Click "Restart" to stop all connections and interrupt all receive/transmit operations, with the following restart of 

the unit. In case of any changes to the parameters, either introduced or stored in the memory, these changes shall 
be implemented. 

 

N o te   -  If  the  addressing  parameters  in  Ethernet  network  (MAC-address,  IP-  address,  DHCP  settings) 

are  modified  and  saved,  the  browser  may  not  load  the  page  after  the  restart  of  the  unit  by  pressing  the 
“Restart”  button.  This  can  happen  as  the  browser  continues  to  reply  over  the  previous  address.  In  this 
case, the connection should be made anew.  

 

Clicking the “Exit” button the will close the setup mode and a password request appears once again. 

 

7.4 CONFIGURING 

ЕТ-485 THROUGH MODBUS INTERFACE 

Setting  via  Modbus-interface  shall  be  provided  if  the  unit  is  connected  over  the  Modbus  client,  which  is 

supporting  the  Modbus  TCP  protocol.  The  connection  is  established  using  its  IP-address  (factory  setting  - 
192.168.0.111) with the indication of Modbus-identifier (factory setting - 111). In the RS-485 slave mode, he setting 
can also be performed by the master device in Modbus network. 

To set the parameters, one should write the password string into the password input parameter (table 6).  
The factory password value is 11111, so to write the factory password into the registers from 0 to 4 one should 

write  the  number  49 

–  the  ASCII  code  of  figure  one.  If  the  password  is  specified  correctly,  the  mode  parameter 

(table 7) obtains the value 1 

– the setting mode. 

In the setting mode, the control command parameter (table 8) as well as the setting parameters (listed in Table 

8) are available for recording. After the necessary values settings are recorded into the parameter registers, one  
should write the value 2 

– “Save” command – into the control command parameter. The correctness of the saved 

parameter values can be checked by comparing the sets of adjustable parameters with the saved parameters. If the 
sets match each other, the new values of settings are accepted and saved. 

To reset the saved parameters to factory values, one should write the value 3 

– “Return to Factory” command –

 

into the control command parameter in the setting mode. 

In order to make the saved parameter values come into effect, the unit must be restarted. By means of Modbus 

interface, the restart is performed by writing the value 1 

– “Restart” command – into the control command parameter 

To exit the setting mode, one should write 0 into the first register of password input parameter. Herewith, all the 

password input registers and the control command parameter register are cleared (obtain 0 value).

 

 

8 COMPLETE SET 

 

ET-485 is supplied with:

 

- ET-485 protocol converter ..................................................... 1 piece 
- Operating manual  ................................................................. 1 piece. 
- Cable for Ethernet connection ............................................... 1 piece 
- Shipping box .......................................................................... 1 piece 

Summary of Contents for ET-485

Page 1: ...perating conditions and wait at least 2 hours before connecting it to the electricity mains Do not use abrasives or organic compounds alcohol gasoline solvents etc for cleaning DO NOT OPEN AND REPAIR...

Page 2: ...6 6 2 Operating 485 over the HTTP protocol 7 6 3 Operating 485 over the Modbus TCP protocol 7 6 4 The operation of ET 485 in the mode of active connection to the client 8 7 SETTINGS 8 7 1 General info...

Page 3: ...onnecting side acts as a server Twisted pair is a pair of insulated conductors inside the cable which are twisted together in order to reduce the distortion of the transmitted signal Indicator is a LE...

Page 4: ...nit to the mains sec no more than 1 Utilized current in case of 220 V mA at most 10 Weight kg at most 0 200 Dimensions mm 95 52 67 Unit purpose Communication equipment Nominal operation condition cont...

Page 5: ...g while data exchange over the Ethernet network Figure 2 Front panel of ET 485 3 2 FUNCTIONING Simplified structural diagram of the unit is provided in Figure 3 32 digit RISC processor with ARM archit...

Page 6: ...CEDURE FOR 485 Suggested maintenance interval every six month The maintenance procedure includes visual inspection to verify the connection of cables to the 485 terminals as well as the absence of fra...

Page 7: ...ddress if connection filtering over IP is activated If this address does not correspond with the preset value the connection is rejected Otherwise the unit starts checking the list of available connec...

Page 8: ...NFIGURATION MAY RESULT IN BLOCKING OR OBSTRUCTION WHILE TRYING TO REACH THE UNIT OVER THE NETWORK In this case all parameters should be factory reset see Section 3 2 7 2 PARAMETERS OF 485 A collection...

Page 9: ...s Mode more detailed see register 141 0 User mode 1 Configuration mode 121 Current IP address IP address of the unit in Ethernet network 122 125 Current MAC address MAC address to authenticate the uni...

Page 10: ...1 the connected client has the permit for setting ET 485 similar to register 121 Bit 8 0 the client is not the main client 1 the client is the main client Bit 9 1 the client has the right for connecti...

Page 11: ...ed 1 setting parameters via Modbus interface or WEB interface is only allowed from the IP address of the main client 526 Enable the IP connections filter over Modbus TCP 0 1 0 0 Modbus TCP connections...

Page 12: ...sponse has not been received within the given time as indicated for the reception of res ponse Waiting time shall not be less then time required for transmission of a single character depending on the...

Page 13: ...additional client having IP address 127 0 0 1 587 Enable the Modbus TCP remote server query redirection mode 0 1 0 0 queries are not sent to remote server 1 queries are additionally sent to Modbus TC...

Page 14: ...ent 0 automatic sending is not accomplished 1 after active connection to the client the unit once sends 1000 1010 registers contents in the form of Modbus response without client query response 1000 1...

Page 15: ...ress IP address DHCP settings are modified and saved the browser may not load the page after the restart of the unit by pressing the Restart button This can happen as the browser continues to reply ov...

Page 16: ...se 9 5 The manufacturer s warranty does not apply to compensation for direct or indirect damages loss or injury associated with transporting the unit to the place of purchase or to the manufacturer 9...

Page 17: ...not necessary for communication between units in a subnet and is only used to connect units of one subnet to units of other networks Factory addressing settings for ET 485 Interface Converter are lis...

Page 18: ...roperties Figure 2 TCP IP properties window in Windows OS window in Windows OS 3 SWITCHING TO INTERNET WARNING The user is strongly recommended to connect the unit to Internet under the supervision of...

Page 19: ...ET 485 IP address filters for recording and or reading can be enabled to provide to a single client the permit to request via Modbus protocol such function codes which are not reading functions unit s...

Page 20: ...direction of queries If the unit whereto the queries are redirected is set to such redirection that the query will be transferred to its initial sender the queries will be transferred nonstop which wi...

Page 21: ...w unit can be specified as the main client It allows increasing the number of RS 485 connected devices and simultaneously connected Modbus TCP clients by 10 for every additional ET 485 unit Each of th...

Page 22: ...g receiving alert messages about incidents via SMS or E Mail Overvis system maintains ACC mode used in ET 485 acting as a data collection server of many simultaneously connected units and providing ac...

Page 23: ...etc b client uses unique MAC address of the unit for its identification In order to provide the access for the user the unique activation code is given to each unit herewith Modbus write protection m...

Page 24: ...ode Symbol 32 64 96 33 65 A 97 A 34 66 B 98 B 35 67 C 99 C 36 68 D 100 D 37 69 E 101 E 38 70 F 102 f 39 71 G 103 g 40 72 H 104 h 41 73 I 105 i 42 74 J 106 j 43 75 K 107 k 44 76 L 108 l 45 77 M 109 m 4...

Page 25: ...AC110 61F GPN V50 AC110 70177 1011 F03 03 HAS B F03 03 HAS C F03 31 81513201 81513535 81550401 FT1A C12RA W 88981106 H2CAC24A R88A CAGA005S R88A CRGB003CR E R88ARR080100S R88A TK01K DCN1 1 DTB4896VRE...

Reviews: