background image

17

 ~

 

NOVATEK-ELECTRO

                                                                                                          ЕТ-485    

 

                                                                                                                                   

 

APPENDIX A 

(recommended) 

 

SWITCHING TO ETHERNET 

 

WARNING! Switching the unit to Ethernet network requires mutual coordination of settings on the 
connected  devices.  Connecting  the  misconfigured  unit  to  the  network  may  affect  the 
communication level of other units on the network. As a rule, all connections to a network of more 

than 2 units are carried out by the qualified personnel (network administrator) only.

 

 

1. IP-ADDRESSING 

When  units  are  communicating  over  Ethernet  network  using  TCP/IP  protocol,  every  unit  is  using  a  set  of  IP-

addressing  settings  to  identify  the  sender  and  receiver  of  the  data.  The  unit  memory  contains  a  personal  and 
unique, within a single subnet, IP-address (four bytes are written as four integers, separated by dots, in the range of 
0-255), subnet mask, which is the same for all units within the subnet (written similar to IP-address), and IP-address 
of  the  gateway,  which  is  used  to  communicate  with  other  networks.  Proper  communication  between  units  of  a 
subnet is possible under several conditions: 

1)All units of a subnet have similar mask. Most of small LANs are using 255.255.255.0 mask. 
2)Mask starts with a group of bits set to 1, followed by a group of bits turned to 0. 
3)All  bits  set  to  1  in  the  mask  are  similar  for  all  the  IP-addresses  of  units  in  subnet  and  indicate  the  subnet 

address. 192.168 is most frequently used address in LANs for the mask 255.255.255.0. The third byte may be used 
as a subnet number in a complex LAN. In smaller LANs, the third byte is usually equal to 0. 

4)A set of bits in IP-address of the unit, which is set to 0 in the mask, is unique to each unit within the same 

subnet . 

5)In  most  cases,  the  unit  like  router,  which  is  already  communicating  with  other  networks,  is  switched  to  the 

network. This unit often gets the following address 192.168.0.1, 192.168.0.100, or 192.168.0.101. In this case, other 
units in the network shall have this IP-address of the unit as the gateway address. This address is not necessary for 
communication between units in a subnet, and is only used to connect units of one subnet to units of other networks. 

Factory addressing settings for ET-485 Interface Converter are listed in Table A.1. 

 

Table 

А.1

 

– Factory settings for ET-485 addressing 

 

Parameter 

Value 

IP-address 

192.168.0.111 

Subnet mask 

255.255.255.0 

Gateway 

192.168.0.1 

 

In  order  to  communicate  with  ET-485,  which  is  set  to  factory  settings,  the  client  unit  (or  any  other  units  on  the 

same  subnet)  should  have  255.255.255.0  as  a  mask  and  address  starting  with  192.168.0.  The  fourth  byte  of  the 
address can take any value in the range from 1 to 255, except for 111. If the connection between ET-485 and a client 
unit is not provided directly but via a network with a number of units, the mentioned address can not be equal to any of 
the addresses of other units on the subnet . If network has several units with the mask and the first three bytes of the 
IP- address, which are different from those specified in Table A.1, or the ET-485 factory IP-address is already taken, 
the  configurable  unit  should  be  temporarily  removed  from  the  network  to  avoid  addressing  conflicts  and  establish  a 
communication  between  this  unit  and  ET-  485  directly.  This  will  allow  to  configure  the  unit  and  ET-485  for  direct 
communication or switching ET-485 to the network. 

 

2. CONFIGURING THE CLIENT UNIT 

The unit addressing is set according to documents and software it uses. 
Below is an example of configuring the personal computer (PC) on Windows XP or Windows 7 to communicate 

directly with the ET-485 on factory settings.

 

 

Open the list of OS network connections to configure the network address in Windows. To do this, follow the 

steps below (mind the OS version): 

For Windows XP: 

1)Log in as administrator. 
2)Select Start-Control Panel. 
3)If control panel items are divided into categories, select "Network and Internet Connections". 
4)Go to "Network Connections". 

 

For Windows 7: 

1)Log in as administrator. 
2)Select Start-Control Panel. 
3)If control panel items are divided into categories, select "Network and Internet". 
4)Go to "Control Center Network and Sharing Center". 
5)In the task bar (on the left), select "Change adapter settings". 

Summary of Contents for ET-485

Page 1: ...perating conditions and wait at least 2 hours before connecting it to the electricity mains Do not use abrasives or organic compounds alcohol gasoline solvents etc for cleaning DO NOT OPEN AND REPAIR...

Page 2: ...6 6 2 Operating 485 over the HTTP protocol 7 6 3 Operating 485 over the Modbus TCP protocol 7 6 4 The operation of ET 485 in the mode of active connection to the client 8 7 SETTINGS 8 7 1 General info...

Page 3: ...onnecting side acts as a server Twisted pair is a pair of insulated conductors inside the cable which are twisted together in order to reduce the distortion of the transmitted signal Indicator is a LE...

Page 4: ...nit to the mains sec no more than 1 Utilized current in case of 220 V mA at most 10 Weight kg at most 0 200 Dimensions mm 95 52 67 Unit purpose Communication equipment Nominal operation condition cont...

Page 5: ...g while data exchange over the Ethernet network Figure 2 Front panel of ET 485 3 2 FUNCTIONING Simplified structural diagram of the unit is provided in Figure 3 32 digit RISC processor with ARM archit...

Page 6: ...CEDURE FOR 485 Suggested maintenance interval every six month The maintenance procedure includes visual inspection to verify the connection of cables to the 485 terminals as well as the absence of fra...

Page 7: ...ddress if connection filtering over IP is activated If this address does not correspond with the preset value the connection is rejected Otherwise the unit starts checking the list of available connec...

Page 8: ...NFIGURATION MAY RESULT IN BLOCKING OR OBSTRUCTION WHILE TRYING TO REACH THE UNIT OVER THE NETWORK In this case all parameters should be factory reset see Section 3 2 7 2 PARAMETERS OF 485 A collection...

Page 9: ...s Mode more detailed see register 141 0 User mode 1 Configuration mode 121 Current IP address IP address of the unit in Ethernet network 122 125 Current MAC address MAC address to authenticate the uni...

Page 10: ...1 the connected client has the permit for setting ET 485 similar to register 121 Bit 8 0 the client is not the main client 1 the client is the main client Bit 9 1 the client has the right for connecti...

Page 11: ...ed 1 setting parameters via Modbus interface or WEB interface is only allowed from the IP address of the main client 526 Enable the IP connections filter over Modbus TCP 0 1 0 0 Modbus TCP connections...

Page 12: ...sponse has not been received within the given time as indicated for the reception of res ponse Waiting time shall not be less then time required for transmission of a single character depending on the...

Page 13: ...additional client having IP address 127 0 0 1 587 Enable the Modbus TCP remote server query redirection mode 0 1 0 0 queries are not sent to remote server 1 queries are additionally sent to Modbus TC...

Page 14: ...ent 0 automatic sending is not accomplished 1 after active connection to the client the unit once sends 1000 1010 registers contents in the form of Modbus response without client query response 1000 1...

Page 15: ...ress IP address DHCP settings are modified and saved the browser may not load the page after the restart of the unit by pressing the Restart button This can happen as the browser continues to reply ov...

Page 16: ...se 9 5 The manufacturer s warranty does not apply to compensation for direct or indirect damages loss or injury associated with transporting the unit to the place of purchase or to the manufacturer 9...

Page 17: ...not necessary for communication between units in a subnet and is only used to connect units of one subnet to units of other networks Factory addressing settings for ET 485 Interface Converter are lis...

Page 18: ...roperties Figure 2 TCP IP properties window in Windows OS window in Windows OS 3 SWITCHING TO INTERNET WARNING The user is strongly recommended to connect the unit to Internet under the supervision of...

Page 19: ...ET 485 IP address filters for recording and or reading can be enabled to provide to a single client the permit to request via Modbus protocol such function codes which are not reading functions unit s...

Page 20: ...direction of queries If the unit whereto the queries are redirected is set to such redirection that the query will be transferred to its initial sender the queries will be transferred nonstop which wi...

Page 21: ...w unit can be specified as the main client It allows increasing the number of RS 485 connected devices and simultaneously connected Modbus TCP clients by 10 for every additional ET 485 unit Each of th...

Page 22: ...g receiving alert messages about incidents via SMS or E Mail Overvis system maintains ACC mode used in ET 485 acting as a data collection server of many simultaneously connected units and providing ac...

Page 23: ...etc b client uses unique MAC address of the unit for its identification In order to provide the access for the user the unique activation code is given to each unit herewith Modbus write protection m...

Page 24: ...ode Symbol 32 64 96 33 65 A 97 A 34 66 B 98 B 35 67 C 99 C 36 68 D 100 D 37 69 E 101 E 38 70 F 102 f 39 71 G 103 g 40 72 H 104 h 41 73 I 105 i 42 74 J 106 j 43 75 K 107 k 44 76 L 108 l 45 77 M 109 m 4...

Page 25: ...AC110 61F GPN V50 AC110 70177 1011 F03 03 HAS B F03 03 HAS C F03 31 81513201 81513535 81550401 FT1A C12RA W 88981106 H2CAC24A R88A CAGA005S R88A CRGB003CR E R88ARR080100S R88A TK01K DCN1 1 DTB4896VRE...

Reviews: