Installation Manual
Technical Specifications
190
Version 3.0
Impedance:
Minimum 500 Ohms, A- in relative
to B- in
Threshold:
Maximum 2 volt and 2 mA
Protection:
±15 volt, A- in relative to B- in, ±50
volt
MOB/ Event input
Insulation:
Maximum ±50 volt, input relative to
power supply lines
Impedance:
3.5 kOhm input relative to Refer-
ence GND
Pull-up:
15 kOhm to internal 12 volt
Threshold:
Positive going maximum 2.3 volt,
input relative to Reference GND
Negative going minimum 0.6 volt,
input relative to Reference GND
Hysteresis minimum 0.6 volt
Protection:
±25 volt, input relative to shield
±50 volt, input relative to external
power lines
Frequency:
Triggered with 50 mS bounce
control
Pulse width:
Minimum 100 mS
Alarm output
Signal levels:
When not in Alarm state, or after
acknowledged alarm: Normally
Open When in Alarm On state:
Closed to Ref. GND
Antenna voltage output
DC voltage:
12 VDC, +1.0 VDC loaded; (11.5
VDC nominal unloaded)
DC current:
Maximum 500 mA at 12.0 volt DC
Summary of Contents for MX500
Page 1: ...oOperator s Installation Manual MX500 Navigation System ...
Page 14: ...Version 3 0 ix Table of Contents Operator s Manual ...
Page 165: ...Version 3 0 151 Configuration Operator s Manual ...
Page 167: ...Version 3 0 153 Datum List Operator s Manual ...
Page 195: ...List of Components Installation Manual Version 3 0 181 APPENDIX F INSTALLATION SECTION ...
Page 196: ...Installation Manual List of Components 182 Version 3 0 SECTION 1 LIST OF COMPONENTS ...
Page 219: ...Installation Notes Version 3 0 205 Installation Manual SECTION 5 INSTALLATION NOTES ...
Page 282: ......
Page 283: ......