5 Parameter
BU 0135 en-4118
91
P499
Function DIP switch
RD
Display range
0 … 6
Other applicable parameter(s):
P108, P130, P428, P570
Arrays
[-01] = Function DIP switch 1
(= value for P428)
[-02] = Function DIP switch 2
(= value for P581)
[-03] = Function DIP switch 3
(= value for P108 (bit 0))
[-04] = Function DIP switch 4
(= value for P108 (bit 1))
Description
Display of functions of DIP switch
(S1)
.
Note
If
P130
=1 is set, all DIP switches are inactive. "0" = "No function" is displayed in all
arrays.
Display values
Value
Meaning
0
No function
The DIP switch is not used
1
Automatic starting
The DIP switch supplies the value for
P428
2
Phase sequence detection
The DIP switch supplies the value for
P581
3 - 4
reserved
5
Switch-off mode bit 0
The DIP switch supplies the value for
P108
– bit 0
6
Switch-off mode bit 1
The DIP switch supplies the value for
P108
– bit 1