NORDAC START (SK 135E / SK 175E) – Users Manual for Motor Starters
64
BU 0135 en-4118
4.2.2.1 Parametrisation
The use of a control and parametrisation unit (SK CSX-3H / SK PAR-3H) or the NORDCON software
is required to adapt the parameters. The most important parameters are shown in the following,
depending on the setting of parameter
P130
:
Parameter group
Parameter numbers
Functions
Comments
Basic parameters
P102 … P103
Start-up and shut-down time
Factory setting:
Value of potentiometer
P4
P108
Switch-off mode
Factory setting:
Value of DIP switch
S1-
DIP3/4
P130
Parameter source
P130
=0
Potentiometer/
Switch
P130
=1
Flash memory
P130=0
(Factory setting):
Potentiometers
(P1-P4)
and
DIP switch
(S1)
effective
P130=1:
Parameter settings effective
Motor data
P203
Rated motor current
Factory setting:
Value of
P1
P210
Start voltage
Factory setting:
Value of potentiometer
P3
Control terminals
P420, P434
Digital inputs and outputs
Factory setting:
See description of
parameter(s)
Additional
parameters
P570
Locking time
Factory setting:
Value of potentiometer
P2
Table 10: Parameters and functions depending on P130
Summary of Contents for NORDAC START Series
Page 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Page 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Page 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Page 119: ...Key word index BU 0135 en 4118 119...
Page 120: ...6071302 4118...