4.2.2.2 Potentiometers P1 to P4
Basic settings for the operation of the motor
starter can be made using potentiometers P1 to
P4. They are non-latching and each one has
10 scale values. The potentiometers are provided
with non-linear characteristic curves at the
software side.
Potentiometer P1
Nominal motor current setting
Device type
Scale value
(Setting in accordance with motor type plate)
[A]
SK 1x5E-301-…
0.9 1.3 1.7 2.3 3.1 4.0 5.5 7.5 9.5 OFF
1)
SK 1x5E-751-…
3.1 4.0 5.5 7.5 9.5 12.5 16.0 19.0 23.5 OFF
1)
1)
I
2
t monitoring deactivated
Figure:
P1 of a 7.5 kW motor starter
Potentiometer P2
Locking time setting
Device type
Scale value
[s]
SK 1x5E-301-…
OFF
1)
0.1 0.2 0.4 0.8 1.6 3.2 6.4 12.8 25.6
SK 1x5E-751-…
1)
Without locking time
Potentiometer P3
Starting torque setting (voltage)
Device type
Scale value
[%]
SK 1x5E-301-…
10
15
20
25
30
40
50
60
80
100
SK 1x5E-751-…
Potentiometer P4
Start-up and shut-down time setting
Device type
Scale value
[s]
SK 1x5E-301-…
OFF
1)
0.1 0.2 0.4 0.8 1.6 3.2 6.4 12.8 25.6
SK 1x5E-751-…
1)
Soft start disabled